6.138
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
Autoreclose Example
Solution
Autoreclose Conditions
The relay initiates three-pole autoreclosing if a Zone 1 trip occurs because of a
multiphase fault.
Circuit Breaker1 attempts the three-pole reclose if Bus 1 is hot and the line is
dead. For this application example, block autoreclose if any of the following
events occur:
➤
Manual trip
➤
Time-delayed trip
➤
Bus trip
➤
Circuit breaker failure trip
If the SEL-421 detects an LOP condition, the autoreclose logic drives the autore-
close function to lockout.
Relay Settings
Select the relay settings for this application example.
Relay Configuration
NOTE:
Setting E79 := Y1 is intended
for certain double circuit breaker
applications. Use E79 := Y for a single
circuit breaker.
Enable reclosing:
E79 :=
Y
.
Reclosing (Y, Y1, N)
Recloser Closing
Select one shot of three-pole autoreclose.
N3PSHOT :=
1
.
Number of Three-Pole Reclosures (N, 1–4)
Use an external switch to select when Circuit Breaker 1 is enabled for three-pole
autoreclose.
E3PR1 :=
IN106
.
Three-Pole Reclose Enable -BK1 (SEL
OGIC
Equation)
If Circuit Breaker 1 fails to close within 10 seconds after the reclose command is
received, the autoreclose logic goes to lockout.
BKCFD :=
600
.
Breaker Close Failure Delay (1–99999 cycles)
Figure 6.35
Circuit Breaker Arrangement at Station S
SEL-421
VAZ
IW
VY
BK1
3
1
3
34
5 kV Bus
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...