6.149
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
Autoreclose and Synchronism-Check Example
You do not need to shift the angle of the synchronism check because both the
source and reference voltage are measured A-Phase-to-neutral.
KS2A :=
0
.
Synch Source 2 Angle Shift (0, 30, 60, 90, 120, 150, 180, 210, 240,
270, 300, 330 degrees)
There is no alternate synchronism source for Circuit Breaker 2 in this application
example.
ALTS2 :=
NA
.
Alternative Synch Source 2 (SEL
OGIC
Equation)
Assume that there is no slip between the source and reference voltages.
25SFBK2 :=
OFF
.
Maximum Slip Frequency—BK2 (OFF, 0.005–0.5 Hz)
Set the maximum allowable voltage angular difference between the source and
reference voltages equal to 20 degrees when attempting to reclose Circuit
Breaker 2.
ANG1BK2 :=
20.0
.
Maximum Angle Difference 1—BK2 (3.0–80 degrees)
Set the maximum allowable voltage angular difference between the source and
reference voltages equal to 20 degrees when attempting to manually close Circuit
Breaker 2.
ANG2BK2 :=
20.0
.
Maximum Angle Difference 2—BK2 (3.0–80 degrees)
The relay does not compensate the synchronism check to account for circuit
breaker closing time because setting 25SFBK2 is OFF. Leave the close time com-
pensation setting at the default.
TCLSBK2 :=
1.00
.
Breaker 2 Close Time (1.00–30 cycles)
Block the synchronism check if Circuit Breaker 2 is closed.
BSYNBK2 :=
52AA2 AND 52AB2 AND 52AC2
.
Block Synchronism Check—
BK2 (SEL
OGIC
Equation)
Example Complete
This completes the application example that describes setting the SEL-421 for
one shot of high-speed single-pole reclosing and one shot of three-pole reclosing
for two circuit breakers. This example showed a configuration for synchronism
check, as well. Analyze your particular power system to determine the appropri-
ate settings for your application.
Relay Settings
provides a list of all the SEL-421 autoreclose settings.
Table 6.40
Settings for Autoreclose and Synchronism Check Example
(Sheet 1 of 3)
Setting
Prompt
Entry
Recloser Closing (Group)
E79
Reclosing (Y, Y1, N)
Y
NSPSHOT
Number of Single-Pole Reclosures (N, 1, 2)
1
ESPR1
Single-Pole Reclose Enable—BK1 (SEL
OGIC
Equation) IN205
ESPR2
Single-Pole Reclose Enable—BK2 (SEL
OGIC
Equation) IN206
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...