6.61
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
Equation 6.22
Z1MP :=
3.2
.
Zone 1 Reach (OFF, 0.05–64
secondary)
Zone 2 Phase-Distance Element Reach
Set Zone 2 phase-distance reach to include the tapped autotransformer.
Perform the following fault study to determine the apparent fault impedance the
SEL-421 distance elements measure for faults at the 138 kV terminals of the
autotransformer. Use these measurements to set the distance reach settings. Sta-
tion R should be in service to account for infeed. Place an AG and ABC fault at
the 138 kV terminals of the autotransformer and record the secondary voltage
and current the relay measures at Station S. Apply these quantities in
, to determine the fault impedance the relay
measures for the two fault types shown in
. Use
for an
A-Phase-to-ground fault and
for the three-phase fault.
Equation 6.23
The relay uses the zero-sequence compensation factor to measure zero-sequence
quantities in terms of positive-sequence quantities.
Equation 6.24
The zero-sequence current is the sum of the phase currents.
Equation 6.25
The magnitude of the impedance for B-Phase-to-C-Phase, B-Phase-to-C-Phase-
to-ground, and three-phase faults is |Z
BC
|.
Equation 6.26
Z1MP
0.8
Z
1L1
Z
+
1L2
•
=
0.8
2 2
+
•
=
3.2
=
where:
V
A
= A-Phase-to-neutral voltage
I
A
= A-Phase current
k
0
= zero-sequence compensation factor
3I
0
= zero-sequence current
where:
V
BC
= B-Phase-to-C-Phase voltage
I
BC
= B-Phase-to-C-Phase current
Z
AG
V
A
I
A
k
0
3I
0
•
+
--------------------------------
=
k
0
Z
0L1
Z
1L1
–
3 Z
1L1
•
------------------------------
=
3I
0
I
A
I
B
I
C
+
+
=
Z
BC
V
BC
I
BC
-----------
=
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...