6.62
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
lists the results of the Z
AG
and Z
BC
calculations.
Select the phase-to-phase measurement from
. Multiply this value by a
safety factor of 125 percent to obtain Zone 2 phase-distance element reach.
Equation 6.27
Z2MP :=
11.00
.
Zone 2 Reach (OFF, 0.05–64
secondary)
Zone 3 Phase-Distance Element Reach
Zone 3 phase-distance protection is reverse-looking. Zone 3 at Station S must
have adequate reach to prevent unwanted tripping by the SEL-421 Relays at Sta-
tions R or T during external faults behind the local terminal. The Zone 3 reach at
Station S must cover overreach from the furthest reaching remote Zone 2 for
reverse faults when there is no infeed from the other remote terminal.
illustrates this coordination issue. You must set the Zone 2 reach at
Station T to account for infeed during faults beyond the tap on the 345 kV sys-
tem. However, when one 345 kV station is out of service, the Zone 2 at Station T
overreaches for faults on the other side of the tap on the 345 kV system.
Place AG and ABC faults at Station T and use
with respect to Station R to record the results in primary. Next place AG and
ABC faults at Station R and use
with respect to
Station T to record the results in primary.
lists the results in primary
and per unit.
Table 6.17
Local Zone 2 Fault Impedance Measurements
Fault Type
|Z
AG
|
|Z
BC
|
AG
7.77
NA
ABC
NA
8.8
Z2MP
1.25 8.8
•
=
11.00
=
Figure 6.13
Reverse Zone 3 Coordination
Z1L3, Z0L3
S
R
T
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...