18.10
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Synchrophasors
Settings for Synchrophasors
FNR
q
Selects the numeric representation, integer (I) or floating-point (F), of the two
frequency values in the synchrophasor data stream
q
.
This setting affects the synchrophasor data packet size.
➤
FNR
q
:= I sends the frequency data as a difference from nominal
frequency, NFREQ, with the following formula.
(FREQPM – NFREQ) • 1000,
represented as a signed, two-byte value. See
for details.
➤
FNR
q
:= I also sends the rate-of-change of frequency data with
scaling.
DFDTPM • 100,
represented as a signed, two-byte value. See
for details.
➤
FNR
q
:= F sends the measured frequency data and rate-of-change-of-
frequency as two four-byte, floating point values.
Phasor Aliases in Data Configuration
q
Phasor Name, Alias Name
This is a freeform setting category with two arguments. Specify the phasor name
and a 16 character descriptive name to be included in the synchrophasor data
stream
q
. If a phasor is not assigned a descriptive name, it will be described using
the phasor name.
Analog Quantities in Data Configuration
q
Analog Quantity Name, Alias Name
This is a freeform setting category with two arguments. Specify the analog quan-
tity name and an optional 16 character descriptive name to be included in the syn-
chrophasor data stream
q
. See
Section 12: Analog Quantities
in the product-
specific instruction manual for a list of analog quantities that the PMU supports.
The PMU can be configured for as many as 16 unique analog quantities for each
data configuration
q
. The analog quantities are floating point values, so each ana-
log quantity the PMU includes will take four bytes.
Digitals in Data Configuration
q
Relay Word Bit Name, Alias Name
This is a freeform setting category with two arguments. Specify the Relay Word
bit name and an optional 16 character descriptive name that you need to include
in the synchrophasor data stream
q
. See the Relay Word Bits section of the relay-
specific instruction manual for a list of Relay Word bits that the PMU supports.
You can configure the PMU for as many as 64 unique digitals for each data con-
figuration.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...