![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 870](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726870.webp)
3.52
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Basic Relay Operations
Reading Oscillograms, Event Reports, and SER
For more information on the event history, see
.
Viewing High-Resolution Oscillograms
Once you have successfully generated an event, you can view high-resolution
oscillograms and event report oscillograms about this event. When gathered from
a field-installed relay, this information helps you assess power system operating
conditions. In addition, when you first install the relay, this reporting information
helps you confirm that you have connected the relay correctly.
The relay provides high-resolution oscillography data in the binary COMTRADE
file format (IEEE/ANSI standard C37.111-1999). File transfer is the only mecha-
nism for retrieving high-resolution COMTRADE data from the relay.
The SEL-5601
SYNCHRO
WAV
E
Event is a program you can use to view COM-
TRADE data. Many third-party software suppliers can provide you with pro-
grams to display and manipulate COMTRADE files.
Retrieving High-Resolution COMTRADE Data in the Terminal
The relay recorded the event triggered in
Generating an Event on page 3.49
. The
procedure in the following steps shows you how to retrieve the high-resolution
raw oscillography data for this event.
Generating an Event on page 3.49
before executing
the instructions in this example. For this procedure, you must use a communica-
tions terminal emulation computer program capable of file transfers.
If you need help finding a terminal emulation program, contact the SEL factory
or your local Technical Service Center.
Step 1. Prepare to monitor the relay at Access Level 1.
a. Using a communications terminal, type
ACC <Enter>
.
b. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1 => prompt.
=>
HIS <Enter>
Relay 1 Date: 03/03/2015 Time: 17:27:44.140
Station A Serial Number: 0000000000
# DATE TIME EVENT LOCAT CURR GRP TARGETS
10024 03/03/2015 08:33:29.201 TRIP $$$$.$$ 0 1
10023 03/02/2015 15:41:35.777 ER $$$$.$$ 0 1
10022 03/02/2015 15:41:35.227 ER $$$$.$$ 0 1
10021 03/02/2015 15:41:34.577 ER $$$$.$$ 0 1
10020 03/02/2015 15:41:34.152 ER $$$$.$$ 0 1
10019 03/02/2015 15:41:32.702 ER $$$$.$$ 0 1
10018 02/24/2015 15:22:19.496 TRIG $$$$.$$ 1 3
10017 02/24/2015 15:22:17.705 TRIG $$$$.$$ 1 3
10016 02/23/2015 17:42:56.581 TRIG $$$$.$$ 1 3
10015 02/20/2015 19:23:41.369 BCG 0.02 3442 3
10014 02/20/2015 17:14:40.056 CA T 7.28 2449 3 TIME A_FAULT C_FAULT
=>
Figure 3.43
Sample HIS Command Output in the Terminal
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...