6.22
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
Breaker Monitor
Circuit Breaker Configuration
Set the relay to indicate that both circuit breakers are single-pole trip type.
BK1TYP :=
1
.
Breaker 1 Trip Type (Single-Pole = 1, Three-Pole = 3)
BK2TYP :=
1
.
Breaker 2 Trip Type (Single-Pole = 1, Three-Pole = 3)
Circuit Breaker 1 Inputs
The SEL-421 uses normally open auxiliary contacts from the circuit breakers to
determine whether each pole is opened or closed.
52AA1 :=
IN101
.
A-Phase N/O Contact Input—BK1 (SEL
OGIC
Equation)
52AB1 :=
IN102
.
B-Phase N/O Contact Input—BK1 (SEL
OGIC
Equation)
52AC1 :=
IN103
.
C-Phase N/O Contact Input—BK1 (SEL
OGIC
Equation)
Circuit Breaker 2 Inputs
52AA2 :=
IN104
.
A-Phase N/O Contact Input—BK2 (SEL
OGIC
Equation)
52AB2 :=
IN105
.
B-Phase N/O Contact Input—BK2 (SEL
OGIC
Equation)
52AC2 :=
IN106
.
C-Phase N/O Contact Input—BK2 (SEL
OGIC
Equation)
Group Settings
Line Configuration
The SEL-421 has four transformer turns ratio settings that convert the secondary
potentials and currents that the relay measures to the corresponding primary val-
ues. These settings are the potential transformer and current transformer ratios
PTRY, PTRZ, CTRW, and CTRX. Use the Y potential input for line relaying and
the Z potential input for synchronism checks. Enable the voltage and current
source selection so you can combine W and X current inputs for the line current.
VNOMY and VNOMZ specify the nominal secondary line-to-line voltage of the
potential transformers (see
Figure 6.4
Circuit Breaker-and-a-Half Arrangement: Station S, Line 1
VY
Circuit 1
VAZ
IX
IW
BK1A
BK1B
SEL-421
1
3
3
3
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...