6.107
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Use the following formula to determine approximately how much primary fault
resistance coverage (R
F
) that 51S1P provides on a radial basis:
Equation 6.66
Use the following as a guide to set the curve and time dial; for secure backup pro-
tection, perform a coordination study. Set the local overcurrent element to coordi-
nate with the downstream overcurrent element so there is a 12-cycle (60 Hz
nominal) safety margin for phase-to-phase (high current) faults in front of the
first downstream overcurrent element. Assume the operating time of the down-
stream overcurrent element is 12 cycles for close-in phase-to-phase faults. There-
fore, set the local time-overcurrent element to operate at approximately 24 cycles
for phase-to-phase faults in front of the first downstream overcurrent element.
The fault current (3I
2
) that the relay measures for a bolted close-in phase-to-
phase fault at the remote station with the parallel cable out of service is 18.67 A
secondary. The pickup multiple is shown in
.
Equation 6.67
Use the parameters of 24 cycles operating time and M = 18.67 to choose the
curve and time dial settings for the 51S1 element. For curve and timing informa-
tion, see
Inverse-Time Overcurrent Elements on page 5.99
51S1C =
U3
.
51S1 Inverse-Time Overcurrent Curve (U1–U5)
51S1TD =
3.72
.
51S1 Inverse-Time Overcurrent Time Dial (0.50–15.0)
Set the overcurrent element to emulate electromechanical reset.
51S1RS =
Y
.
51S1 Inverse-Time Overcurrent EM Reset (Y, N)
Torque control the overcurrent element with the forward decision from the
ground directional element.
51S1TC =
32GF
.
51S1 Torque Control (SEL
OGIC
Equation)
Zone/Level Direction
Zone 1 and Zone 2 distance element directions are fixed in the forward direction.
You can select the other zones independently as forward-looking (F), or reverse-
looking (R). Set Zone 3 distance elements reverse-looking; these are blocking
elements for the POTT scheme.
DIR3 :=
R
.
Zone/Level 3 Directional Control (F, R)
R
F
PTR
CTR
------------
VNOMY
3
------------------------
51S1P
---------------------------
•
=
2000
200
------------
115 V
3
---------------
1.00 A
----------------
•
=
664
primary
=
M
I
2FAULT
51S1P
---------------------
=
18.67 A
1.00 A
-------------------
=
18.67
=
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...