6.21
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
Global Settings
General Global Settings
The SEL-421 has settings for identification. These settings allow you to identify
the following:
➤
Station (SID)
➤
Relay (RID)
➤
Circuit Breaker 1 (BID1)
➤
Circuit Breaker 2 (BID2)
You can enter as many as 40 characters per identification setting.
SID :=
MOSCOW — 500 kV
.
Station Identifier (40 characters)
RID :=
SEL-421 Relay
.
Relay Identifier (40 characters)
Configure the SEL-421 for two circuit breakers. This particular application uses
two circuit breakers because the terminal is a circuit breaker-and-a-half configu-
ration.
NUMBK :=
2
.
Number of Breakers in Scheme (1, 2)
BID1 :=
Circuit Breaker 1
.
Breaker 1 Identifier (40 characters)
BID2 :=
Circuit Breaker 2
.
Breaker 2 Identifier (40 characters)
You can select both the nominal frequency and phase rotation.
NFREQ :=
60
.
Nominal System Frequency (50, 60 Hz)
PHROT :=
ABC
.
System Phase Rotation (ABC, ACB)
Current and Voltage Source Selection
The voltage and current source selection is for two circuit breakers in a circuit
breaker-and-a-half configuration. Set ESS to 3.
ESS :=
3
.
Current and Voltage Source Selection (Y, N, 1, 2, 3, 4)
After you select 3 for setting ESS, the relay automatically sets LINEI, BK1I, and
BK2I as follows:
LINEI :=
COMB
.
Line Current Source (IW, COMB)
BK1I :=
IW
.
Breaker 1 Current Source (IW, IX, NA)
BK2I :=
IX
.
Breaker 2 Current Source (IW, IX, NA)
In this application example Circuit Breaker BK1A is Breaker 1 in the relay set-
tings and BK1B is Breaker 2 in the relay settings.
illustrates the current and voltage sources for this particular applica-
tion. The relay uses potential input VY and the combination of current inputs IW
and IX for line relaying; potential input VAZ is for synchronism check.
close and Synchronism Check Example on page 6.141
describes how to apply the
synchronism-check function.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...