14.6
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
ASCII Command Reference
Command Description
CBREAKER
NOTE:
Not all SEL-400 series relays
support breaker monitoring
The
CBREAKER
command provides a Compressed ASCII response circuit
breaker report that is similar to the
BREAKER
command. You must enable the
Breaker Monitor function for at least one breaker to generate the Compressed
ASCII report. You can specify a specific circuit breaker to retrieve a report for
one circuit breaker only. See
SEL Compressed ASCII Commands on page 15.24
for information on the Compressed ASCII command set.
CBR
Use the
CBR
command to gather the comprehensive circuit breaker report in
Compressed ASCII format.
CBR TERSE
The
CBR TERSE
command omits the breaker report labels.
CEVENT
The
CEVENT
command provides a Compressed ASCII response similar to the
EVENT
command. See
SEL Compressed ASCII Commands on page 15.24
for
information on the Compressed ASCII command set.
CEV
Use the
CEV
command to gather relay event reports. When parameter
n
is 1–9999,
n
indicates the order of the event report. The most recent event report is 1, the
next most recent report is 2, and so on. When parameter n is 10000–42767,
n
indicates the absolute serial number of the event report.
Table 14.15
CBR Command
Command
Description
Access Level
CBR
Return the most recent circuit breaker reports for all circuit
breakers in Compressed ASCII format.
1, B, P, A, O, 2
CBR
n
a
a
Parameter
n
= breaker identification character.
Return the most recent circuit breaker report for Circuit
Breaker
n
in Compressed ASCII format.
1, B, P, A, O, 2
Table 14.16
CBR TERSE Command
Command
Description
Access Level
CBR TERSE
Return the most recent circuit breaker report for all cir-
cuit breakers in Compressed ASCII format; suppress the
labels; transmit only the data lines.
1, B, P, A, O, 2
CBR
n
a
TERSE
a
Parameter
n
= breaker identification character.
Return the most recent circuit breaker report for Circuit
Breaker
n
in Compressed ASCII format; suppress the
labels; transmit only the data lines.
1, B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...