SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Basic Relay Operations
Reading Oscillograms, Event Reports, and SER
Step 1. Prepare to control the relay at Access Level 2.
a. Using a communications terminal, type
ACC <Enter>
.
b. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1 => prompt.
c. Type
2AC <Enter>
.
d. Type the correct password to go to Access Level 2.
You will see the Access Level 2 =>> prompt.
Step 2. Enter SER trigger data.
a. Type
SET R TERSE <Enter>
to access the
Report
settings (see
b. Press
<Enter>
to move past the
SER Chatter Criteria
setting.
c. At the
SER Points
?
prompt line, type the following:
TRGTR,“TARGET RESET PB”,TEST,OFF,N <Enter>
.
At the next line, type
END <Enter>
.
d. The relay prompts you to save the new setting; type
Y <Enter>
.
Step 3. Press and release the front-panel
TARGET RESET
pushbutton to generate
an SER record.
Step 4. Type
SER <Enter>
(at the Access Level 1 prompt or higher) to view
the SER report.
The relay presents a screen similar to the SER display of
.
Downloading an SER Report File
The procedure in the following steps shows you how to retrieve the SER report
stored in the relay as a file. For this procedure, you must use a terminal emulation
program with file transfer capability.
Step 1. Prepare to monitor the relay at Access Level 1.
a. Using a communications terminal, type
ACC <Enter>
.
b. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1 => prompt.
Step 2. Type
FILE DIR REPORTS <Enter>
to view the events file direc-
tory.
The terminal lists the file names for standard reports as shown in
.
=>>
SET R TERSE <Enter>
Report
SER Chatter Criteria
Automatic Removal of Chattering SER Points (Y,N) ESERDEL := N ?
<Enter>
SER Points
(Relay Word Bit, Reporting Name, Set State Name, Clear State Name, HMI Alarm)
1:
?
TRGTR,“TARGET RESET PB”,TEST,OFF,N <Enter>
2:
?
END <Enter>
Save settings (Y,N) ?
Y <Enter>
Saving Settings, Please Wait...........
Settings Saved
=>>
Figure 3.53
Setting an SER Element: Terminal
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...