12.10
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Settings
Port Settings
Make
settings if Port setting PROTO := DNP.
SVT
p
ICH
SVTX
p
Channel Current Terminal (W,X)
W
SVT
p
VCH
SVTX
p
Channel Voltage Terminal ([range])
Y
a
p
represents the publication number. Seven publications are supported. Only settings for
publications enabled by SVTXEN will be visible.
b
Layer 2 multicast address only. Broadcast address is not allowed.
c
The 0x prefix is used to indicate that this setting is in hexadecimal.
Table 12.16
DNP3 Serial Protocol Settings (Sheet 1 of 2)
Label
Prompt
Default Value
DNPADR
DNP Address (0–65519)
0
DNPID
DNP ID for Object 0, Var 246 (20 characters)
“Relay 1-DNP”
DNPMAP
DNP Session Map (1–5)
1
ECLASSB
Class for Binary Event Data (OFF, 1–3)
1
ECLASSC
Class for Counter Event Data (OFF, 1–3)
OFF
ECLASSA
Class for Analog Event Data (OFF, 1–3)
2
ECLASSV
Class for Virtual Terminal Data (OFF, 1–3)
OFF
TIMERQ
Time-Set Request Interval (I, M, 1–32767 minutes)
I
DECPLA
Currents Scaling (0–3 decimal places)
1
DECPLV
Voltages Scaling (0–3 decimal places)
1
DECPLM
Misc Data Scaling (0–3 decimal places)
1
STIMEO
Select/Operate Time-Out (0.0–60.0 seconds)
1.0
DRETRY
Data Link Retries (OFF, 1–15)
OFF
DTIMEO
Data Link Time-Out (0.0–30.0 seconds)
1
MINDLY
Minimum Delay from DCD to TX (0.00–1.00 seconds)
0.05
MAXDLY
Maximum Delay from DCD to TX (0.00–1.00 seconds)
0.10
PREDLY
Settle Time-RTS On to TX (OFF, 0.00–30.00 seconds)
0.00
PSTDLY
Settle Time-TX to RTS Off (0.00–30.00 seconds)
0.00
DNPCL
Enable Control Operations (Y, N)
N
AIVAR
Default Variation for Analog Inputs (1–6)
2
ANADBA
Analog Reporting Deadband for Currents (0–32767)
100
ANADBV
Analog Reporting Deadband for Voltages (0–32767)
100
ANADBM
Analog Reporting Deadband (0–32767)
100
ETIMEO
Event Message Confirm Time-Out (1–50 seconds)
2
UNSOL
Enable Unsolicited Reporting (Y, N)
N
PUNSOL
Enable Unsolicited Reporting at Power-Up (Y, N)
N
REPADR
DNP Address to Report to (0–65519)
1
NUMEVE
Number of Events to Transmit On (1–200)
10
AGEEVE
Age of Oldest Event to Transmit On (0–99999)
2
URETRY
Unsolicited Message Max Retry Attempts (2–10)
3
UTIMEO
Unsolicited Message Offline Time-Out (OFF, 1–5000 sec)
60
EVEMOD
Event Mode (SINGLE, MULTI)
SINGLE
Table 12.15
SV Transmitter Configuration (Sheet 2 of 2)
Label
Prompt
Default Value
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...