17.11
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
IEC 61850 Communication
IEC 61850 Operation
Similarly, for unbuffered reports, connected clients may edit the report parame-
ters shown in
.
For buffered reports, only one client can enable the RptEna attribute of the BRCB
at a time resulting in a client association for that BRCB. Once enabled, the asso-
ciated client has exclusive access to the BRCB until the connection is closed or
the client disables the RptEna attribute. Once enabled, all unassociated clients
have read only access to the BRCB.
For unbuffered reports, as many as seven clients can enable the RptEna attribute
of an URCB at a time resulting in multiple client associations for that URCB.
Once enabled, each client has independent access to a copy of that URCB.
The Resv attribute is writable, however, the relay does not support reservations.
Writing any field of the URCB causes the client to obtain their own copy of the
URCB-in essence, acquiring a reservation.
Reports are serviced at a 2 Hz rate. The client can set the IntgPd to any value with
a resolution of 1 ms. However, the integrity report is only sent when the period
has been detected as having expired. The report service rate of 2 Hz results in a
report being sent within 500 ms of expiration of the IntgPd. The new IntgPd will
begin at the time that the current report is serviced.
Datasets
IEC 61850 datasets are lists of references to DataObject attributes for the purpose
of efficient observation and transmission of data. Architect ICD files come with
predefined datasets that can be used to transfer data via GOOSE messages, SV
messages, or MMS reports.
➤
GOOSE: You can use predefined or edited datasets, or create new
datasets for outgoing GOOSE transmission.
➤
SV: Four predefined datasets are provided. Each dataset includes
three phase currents and the neutral current as well as three phase
voltages and the neutral voltage.
Table 17.6
Unbuffered Report Control Block Client Access
RCB Attribute
User Changeable
(Report Disabled)
User Changeable
(Report Enabled)
Default Values
RptID
YES
URep01–URep07
RptEna
YES
YES
FALSE
Resv
YES
FALSE
OptFlds
YES
seqNum
timeStamp
dataSet
reasonCode
BufTm
YES
250
TrgOps
YES
dchg
qchg
period
IntgPd
YES
0
GI
YES
a
a
Exhibits a pulse behavior. Write a one to issue the command. Once command is accepted will
return to zero. Always read as zero.
FALSE
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...