6.166
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
Circuit Breaker Failure Application Examples
Assign the protection elements to Relay Word bits BFIA1, BFIB1, and BFIC1 to
initiate single-pole trip circuit breaker failure protection for Circuit Breaker BK1.
For a complete description of circuit breaker failure initiation, see
Breaker Failure Protection on page 5.146
. This application example uses the
POTT tripping scheme, step-distance backup protection, and SOTF protection.
BFIA1 :=
BFIAT1 OR TPA1
.
A-Phase Breaker Failure Initiate—BK1
(SEL
OGIC
Equation)
BFIB1 :=
BFIBT1 OR TPB1
.
B-Phase Breaker Failure Initiate—BK1
(SEL
OGIC
Equation)
BFIC1 :=
BFICT1 OR TPC1
.
C-Phase Breaker Failure Initiate—BK1
(SEL
OGIC
Equation)
Relay Word bits BFIAT1, BFIBT1, and BFICT1 (Circuit Breaker 1 Latched Sin-
gle-Pole Circuit Breaker Failure Initiation) latch the BFIA1, BFIB1, and BFIC1
inputs to the circuit breaker failure protection.
Circuit Breaker Failure Protection Initiation Dropout Delay
Set the circuit breaker failure initiate time delay on dropout to stretch a short
pulsed circuit breaker failure initiation. Enable this feature for this application
example because you are protecting dual circuit breakers.
BFIDO1 :=
3.000
.
Breaker Failure Initiate Dropout Delay—BK1
(0.000–1000 cycles)
Circuit Breaker Failure Protection Initiation Seal-In Delay
Set the circuit breaker failure initiate time delay on pickup for the latch logic to
qualify extended circuit breaker failure initiation latch seal-in.
BFISP1 :=
4.000
.
Breaker Failure Initiate Seal-In Delay—BK1
(0.000–1000 cycles)
For these BFIDO1 and BFISP1 settings, if the circuit breaker failure initiate is 1
cycle or more, the relay seals in the circuit breaker failure extended initiation
after the initiate signal deasserts until the BFIDO1 time (3 cycles) expires and all
50F
1 elements deassert.
Residual Current Circuit Breaker Failure Protection
Disable residual current circuit breaker failure protection for Circuit Breaker
BK1 because a strong source drives this terminal.
ENCBF1 :=
N
.
No Current/Residual Current Logic—BK1 (Y, N)
Load Current Circuit Breaker Failure Protection
Disable load current circuit breaker failure protection for Circuit Breaker BK1.
ELCBF1 :=
N
.
Load Current Breaker Failure Logic—BK1 (Y, N)
Flashover Circuit Breaker Failure Protection
Disable flashover current circuit breaker failure protection for Circuit Breaker
BK1.
EFOBF1 :=
N
.
Flashover Breaker Failure Logic—BK1 (Y, N)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...