6.119
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
Out-of-Step Logic Application Examples
Out-of-Step Logic Application Examples
The SEL-421 features OOS (out-of-step) logic for the following two functions:
➤
OSB (out-of-step blocking) logic blocks phase-distance elements and
Zone 1 ground-distance elements during power swings.
➤
OST (out-of-step tripping) logic trips the circuit breaker(s) during
unstable swings.
There are two application examples that explain how to apply OOS logic: an out-
of-step blocking scheme and an out-of-step tripping and blocking scheme. The
examples provide detailed setting procedures for a 5 A relay.
These examples are for three-pole tripping in a 500 kV power system. Applica-
tions for single-pole tripping are similar. Refer to
for a one-line dia-
gram of the 500 kV system.
Z2GTSP
Zone 2 Ground Distance Time Delay SPT (Y, N)
N
67QGSP
Zone 2 Dir. Negative-Sequence/Residual Overcur-
rent Single Pole Trip (Y, N)
N
TDUR1D
SPT Min Trip Duration Time Delay
(2.000–8000 cycles)
6.000
TDUR3D
3PT Min Trip Duration Time Delay
(2.000–8000 cycles)
9.000
E3PT
Three-Pole Trip Enable (SEL
OGIC
Equation)
1
E3PT1
Breaker 1 3PT (SEL
OGIC
Equation)
1
ER
Event Report Trigger (SEL
OGIC
Equation)
R_TRIG Z2P OR
R_TRIG Z2G OR
R_TRIG 51S1 OR
R_TRIG Z3P OR
R_TRIG Z3G
Main Board (Outputs)
OUT101
(SEL
OGIC
Equation)
3PT
OUT102
(SEL
OGIC
Equation)
KEY
a
Parameter
n
is 1 for BK1, 2 for BK2, and L for Line.
Table 6.31
Settings for 230 kV Parallel Cables Example (Sheet 5 of 5)
Setting
Prompt
Entry
Figure 6.28
500 kV Power System
SEL-421
Z1L1
Z1R
Z1S
S
R
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...