SEL-400 Series Relays
Synchrophasors
Settings for Synchrophasors
➤
PMOTS[2] := UDP_T establishes two socket connections. A
nonpersistent TCP connection is used for receiving synchrophasor
command messages as well as synchrophasor configuration and
header response messages. A persistent UDP connection is used to
transmit synchrophasor data messages.
depicts the
UDP_T connection.
➤
PMOTS[2] := UDP_U uses the same connection scheme as the
UDP_T except the synchrophasor configuration and header response
messages are sent over the UDP connection, as shown in
.
➤
PMOTS[2] := UDP_S establishes a single persistent UDP socket to
transmit synchrophasor messages. Synchrophasor data are
transmitted whenever new data are read. With this communications
scheme, the relay sends a “Synchrophasor Configuration
Response 2” once every minute, as shown in
PMODC[2]
NOTE:
If PMODC is set to a number
that exceeds the setting for
NUMPHDC, the port sends the data for
the first PMU configuration.
Select the data configuration (1-NUMPHDC) for synchrophasor data transmis-
sion on the specific session 1 and 2. Using this setting, each Ethernet session can
be configured to stream unique synchrophasor data.
PMOIPA[2]
Defines the PMU Output Client IP address for session 1 and 2, respectively.
PMOTCP[2]
Defines the TCP/IP (Local) port number for session 1 and 2, respectively. These
port numbers must all be unique.
PMOUDP[2]
Defines the UDP/IP (Remote) port number for session 1 and 2, respectively.
Figure 18.4
UDP_T and UDP_U Connections
Figure 18.5
UDP_S Connection
C37.118
- Synchrophasor Command Start Request
- Synchrophasor Command Stop Request
- Synchrophasor Command Configuration Request 1
- Synchrophasor Command Configuration Request 2
- Synchrophasor Command Header Frame Request
- Synchrophasor Command Extended Frame
If PMOTS[2] is UDP_T
- Synchrophasor Configuration Response 1
- Synchrophasor Configuration Response 2
- Synchrophasor Header Frame Response
C37.118
- Synchrophasor Measurement
If PMOTS[2] is UDP_U
- Synchrophasor Configuration Response 1
- Synchrophasor Configuration Response 2
- Synchrophasor Header Frame Response
TCP Socket
(Persistent)
UDP Socket
(Persistent)
SEL-400
C37.118
- Synchrophasor Measurement
- Synchrophasor Configuration Response 2
(Sent once per minute)
UDP Socket
(Persistent)
SEL-400
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...