6.112
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Weak Infeed
The SEL-421 provides weak-infeed logic to high-speed trip both line terminals
for internal faults near the weak terminal. The weak terminal echoes the permis-
sive signal back to the strong terminal and causes the strong terminal to trip. The
weak terminal trips by converting the echoed permissive signal to a trip signal if
specific conditions are satisfied.
This application example does not use the weak-infeed feature.
EWFC :=
N
.
Weak Infeed Trip (Y, N, SP)
Permission to Trip Received
Assign a control input to receive trip permission from the remote terminal.
PT1 :=
IN103
.
General Permissive Trip Received (SEL
OGIC
Equation)
Trip Logic
Trip logic configures the relay for tripping. There are four trip logic settings com-
ponents:
➤
Trip equations
➤
Trip unlatch options
➤
Trip timers
➤
Three-pole tripping enable
Trip Equations
Set these three SEL
OGIC
control equations for tripping:
➤
TR (unconditional)
➤
TRCOMM/TRCOMMD (communications-assisted; in this example
we use only TRCOMM)
➤
TRSOTF (SOTF)
TR
The TR SEL
OGIC
control equation determines which protection elements cause
the relay to trip unconditionally. Set TR to the Zone 1 instantaneous distance pro-
tection (Z1T), Zone 2 time-delayed distance protection, and the inverse-time
overcurrent element (51S1) for backup protection. For information on setting
51S1, see
Selectable Operating Quantity Time Overcurrent Element 1 on
TR :=
Z1T OR Z2T OR 51S1T
.
Trip (SEL
OGIC
Equation)
TRCOMM
The TRCOMM SEL
OGIC
control equation determines which elements trip via
the communication-assisted tripping logic. In the TRCOMM SEL
OGIC
control
equation, set Zone 2 mho phase-distance protection for phase faults, and Level 2
negative-sequence directional overcurrent element (67Q2) for ground faults.
TRCOMM :=
Z2P OR 67Q2
.
Communications-Assisted Trip (SEL
OGIC
Equation)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...