![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 89](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726089.webp)
2.39
Date Code 20171021
Instruction Manual
SEL-421 Relay
Installation
Connection
The SEL-2243 has sufficient power capacity to accommodate an entire Axion
node. The terminal strip at the bottom of the unit (shown in
) is the
connection point for incoming power. All Axion modules have a 55-position IEC
C-style connector that provides a communications and power interface to the
backplane. See the
SEL-2240 Axion Instruction Manual
for more information.
SEL-2244-2 Digital Input Module
The SEL-2244-2 Digital Input Module (see
) consists of 24 optoiso-
lated inputs that are not polarity dependent. These inputs can be configured to
respond to ac or dc control signals. The TiDL system maps as many as 72 DI
points to the relay in the 300, 400, and 500 I/O board levels, based on the mod-
ules that occur in the network. Only the first 12 of 24 inputs are used in each
module to help distribute the I/O around the network more efficiently. The inputs
are mapped to the relay inputs based on the order in which the DI module occurs
in the TiDL network.
There can be multiple DI modules in an Axion node, and the order of the DI
modules will proceed from left to right in the node to determine the mapping of
the inputs.
The first DI module that exists in the system, for example, on
PORT 6A
, will map
to
IN301
–
IN312
, and if a second module is available on
PORT 6A
, it will map to
IN313
–
IN324
. If a second module does not exist on
PORT 6A
,
IN313
–
IN324
will be
mapped from the next module appearing in the TiDL system. Mapping order
determination starts with
PORT 6A
and ends with the last port,
PORT 6H
.
Figure 2.39
SEL-2243 Power Coupler
First SEL-2244-2 DI Module
IN301–IN312
Second SEL-2244-2 DI Module
IN313–IN324
Third SEL-2244-2 DI Module
IN401–IN412
Fourth SEL-2244-2 DI Module
IN413–IN424
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...