9.6
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Reporting
Triggering Data Captures and Event Reports
Triggering Data Captures and Event Reports
Oscillograms and event reports are triggered both internally and externally
depending on the event trigger that you program in the relay.
Use an event trigger to initiate capturing power system data. High-resolution raw
data oscillography and event reports use the same triggering methods. The trigger
for data captures comes from three possible sources:
➤
Relay Word bit TRIP assertions
➤
SEL
OGIC
control equation ER (Event Report Trigger)
➤
TRI
command
In some SEL relays, the
PUL
command initiated event recording. If you want the
PUL
command to initiate data capture, add the Relay Word bit TESTPUL to the
SEL
OGIC
control equation ER.
Relay Word Bit TRIP
If Relay Word bit TRIP asserts, the relay automatically generates a data capture
event trigger on the rising edge of the TRIP Relay Word bit state change. In every
instance, TRIP causes the relay to begin recording data. You therefore do not
have to enter any condition that causes a trip in the ER SEL
OGIC
control equa-
tion.
SEL
OGIC
Control Equation ER
Program the SEL
OGIC
control equation ER to trigger high-resolution raw data
oscillography, traveling wave data oscillography, and standard event reports for
conditions other than TRIP conditions. When ER asserts, the relay begins record-
ing data if the relay is not already capturing data initiated by another trigger.
Example 9.1
Triggering Event Report/Data Capture Using the ER SEL
OGIC
Control Equation
This example shows how the elements in the ER SEL
OGIC
control equation
initiate relay data capture.
An example of a factory default setting for Group setting SEL
OGIC
control
equation ER in the SEL-411L is
ER :=
R_TRIG Z2P OR R_TRIG Z2G OR R_TRIG 51S01 OR
R_TRIG Z3P OR R_TRIG Z3G
Event Report Trigger Equation
(SEL
OGIC
Equation)
The element transitions in this setting are from the following Relay Word
bits:
➤
Z2P, Z3P: Zone 2 phase-distance element, Zone 3 phase-
distance element
➤
Z2G, Z3G: Zone 2 ground-distance element, Zone 3 ground-
distance element
➤
51S01: Instantaneous output of Inverse-Time Overcurrent
Element 1
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...