13.18
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
SEL
OGIC
Control Equation Programming
SEL
OGIC
Control Equation Elements
Set the conditioning timer settings for Pickup and Dropout in cycles and fractions
of a cycle (represented in decimal form). The relay processes conditioning timers
once for each protection processing interval. The relay asserts the timer output on
the first processing interval when the elapsed time exceeds the setting. In most
SEL-400 series relays, the protection processing interval is 1/8 cycle (or 0.125 cycles).
See the product-specific instruction manual to determine the specific processing inter-
val. Actual settings, programming, and operation are illustrated in
Figure 13.6
Conditioning Timer With Pickup and Dropout Timing Diagram
Example 13.7
Conditioning Timer Programming and Operation
This example uses protection freeform conditioning timer seven, PCT07.
The freeform settings are as shown here:
PCT07PU :=
5.3
# Pickup set to 5.3 cycles
PCT07D0 :=
6.0
# Dropout set to 6.0 cycles
PCT07IN :=
IN101
# Operate on the first input on the main board
PSV29 :=
PCT07Q
# Protection SEL
OGIC
control equation variable fol-
lows the timer output
The operation of the timer when IN101 turns on for 7 cycles is shown in the
timing diagram in
. Because the pickup setting is an uneven num-
ber of protection processing intervals (1/8 cycle), the pickup occurs on the
first 1/8th cycle after the Pickup Time of 5.3 cycles expires.
PCT03IN
PCT03Q
Input Changes
from 0 to 1
Input Changes
from 1 to 0
Dropout Time
Expires
Pickup Time
Expires
Dropout Time
PCT03DO
Pickup
Time
PCT03PU
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...