6.135
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
Out-of-Step Logic Application Examples
Out-of-Step Block Time Delay
Set OSBD longer than OSTD by the next timer setting step (0.125-cycle step
size) greater than 0.500 cycle. Thus, the OSBD setting is calculated in
Equation 6.87
OSBD :=
1.500
.
Out-of-Step Block Time Delay (0.500–8000 cycles)
To find the effective slip rate for OOS blocking, solve
for f
slip
.
Equation 6.88
The relay detects OOS blocking conditions for power swing slip frequencies up
to 5.95 Hz and OOS tripping conditions for power swing slip frequencies from
5.95 Hz to 10.2 Hz (see
). Zone 1 and Zone 2 elements remain
blocked during these OSB and OST conditions. The event is not a swing condi-
tion if the Z
1
impedance locus crosses Zone 7 and Zone 6 before the OSTD and
OSBD timers time out. The relay identifies this event as a fault condition.
Latch Out-of-Step Blocking
Latch out-of-step blocking to maintain the blocking condition throughout the
entire swing cycle.
OSBLTCH :=
Y
.
Latch Out-of-Step Blocking (Y, N)
Control Outputs
For local OOS tripping, configure the relay control outputs for tripping and
remote notification of an out-of-step condition. Include Relay Word bit OST in
the direct tripping SEL
OGIC
control equation TR. (Add
OR OST
to the existing
TR equation; the default is shown here.)
TR :=
Z1P OR Z1G OR M2PT OR Z2GT OR OST
.
Trip (SEL
OGIC
Equation)
Set a control output for remote notification of the out-of-step tripping condition.
This example uses OUT205. Select a relay control output that is appropriate for
your particular application.
OUT205 :=
OST
.
Output OUT205 (SEL
OGIC
Equation)
OSBD
OSTD 0.500 cycle timer step
+
+
=
0.875 0.500 0.125
+
+
=
1.500 cycles
=
f
slip
Ang_R6 Ang_R7
–
f
NOM
•
360
cycle
------------
OSBD
•
---------------------------------------------------------------------------
=
120.0
66.4
–
60 Hz
•
360
cycle
------------
1.500 cycle
•
--------------------------------------------------------------
=
5.5 Hz
=
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...