6.102
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
k0M :=
6.105
.
Forward Zones ZSC Factor Magnitude (0.000–10)
k0A :=
44.5
.
Forward Zones ZSC Factor Angle (–180.0 to +180.0 degrees)
k0MR :=
6.105
.
Reverse Zones ZSC Factor Magnitude (0.000–10)
k0AR :=
44.5
.
Reverse Zones ZSC Factor Angle (–180.0 to +180.0 degrees)
Distance Element Common Time Delay
Set the operation time delay of both the phase and ground-distance elements.
Zone 1
There is no need to delay Zone 1 distance protection; the relay trips instanta-
neously for faults in Zone 1.
Z1D =
0.000
.
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
Zone 2
Zone 2 distance protection must coordinate with downstream Zone 1 distance
protection plus the downstream circuit breaker operating time and a safety mar-
gin. A typical Zone 2 phase and ground-distance time delay setting is 20 cycles.
Z2D :=
20.000
.
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
Short Adjacent Lines
You do not need to consider the following fault current return path scenario for
this application example; this information is provided here for applications with
short adjacent lines.
illustrates an important consideration if you
apply time-delayed Zone 2 ground-distance protection to backup downstream
Zone 1 ground-distance protection.
Fault current flows through the sheath and ground with respect to the cable
because the sheath is grounded at each end during external ground faults. How-
ever, because you must make sure that Zone 2 ground-distance elements see all
ground faults at remote Station R, the k0 setting was for the ground path only.
Therefore, Zone 2 ground-distance protection may overreach for external ground
faults, especially for the case of a short adjacent line. The solution is to increase
Zone 2 time delay.
Figure 6.25
External Ground Fault
SEL-421
Conductor
I
F
I
C
I
S
I
G
Sheath
Ground
R
S
Zone 2 Ground Distance
Zone 1 Ground Distance
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...