5.20
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Control
Bay Control Front-Panel Operations
If Relay Word bit 89CCM1 asserts after you press the
ENT
key, the relay displays
the screen with the caption
CLOSE COMMAND ISSUED
in
Figure 5.12(c)
for three
seconds. While the disconnect operation is in progress, the relay displays the
screen with the caption
IN PROGRESS
in
and the disconnect sym-
bol alternately displays the present state symbol and the opposite state symbol. If
another disconnect operation attempt is made while a disconnect operation is in
progress, the relay displays the screen with the caption
*NOT ALLOWED*
in
Figure 5.13(b)
for three seconds and then the relay returns to the screen in
Figure 5.13(a)
.
If Relay Word bit 89CCM1 does not assert, the relay displays the
*NOT ALLOWED*
error message shown in
for three seconds and then displays again
the screen in
Figure 5.12(b)
.
When Relay Word bit 89CCMD1 asserts, the Close Immobility Timer starts. If
Relay Word bit 89CCMD1 asserts, two scenarios are possible: the disconnect
fails to close, or the disconnect closes successfully. In the case of a successful
close operation, the relay displays the screen in
Figure 5.14(b)
.
Failing to close also has two possible scenarios: the disconnect starts to move, but
does not complete the operation, or the disconnect switch operation does not initiate.
When Relay Word bit 89OPN1 deasserts, the Close Immobility timer resets, indi-
cating that the disconnect switch has started to move. If Relay Word bit 89CL1
fails to assert in the expected operation time, the disconnect switch has failed to
complete the close operation in the expected time. Failure of the 89CL1 Relay
Word bit to assert in the expected disconnect switch operation time causes the
89AL1 Relay Word bit to assert. When Relay Word bit 89AL1 asserts, the relay
displays the screen
Figure 5.14(a)
(see
Disconnect Switch Status and Alarm
If Relay Word bit 89OPN1 fails to deassert before the Close Immobility Timer
expires, Relay Word bit 89ICM1 asserts and the relay displays the screen with the
caption
STATUS UNKNOWN
in
. See
Open Immobility Timer Logic on page 5.8
for more information regarding the
close and open immobility timer logic.
When the disconnect operation completes successfully, the relay displays the
screen in
until the front-panel timer times out or the
ESC
pushbut-
ton is pressed.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...