SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Basic Relay Operations
Examining Metering Quantities
Step 7. Turn the relay on.
Step 8. View metering.
a. Type
ACC <Enter>
to log in to the relay at Access Level 1.
b. Type the password and press
<Enter>
.
c. Type
MET <Enter>
.
The relay displays the fundamental frequency (50 Hz or 60 Hz)
metering information in a manner similar to that shown in
.
View Metering Using the Terminal on page 3.35
are
the fundamental line quantities. Other variants of the
MET
command give differ-
ent relay metering quantities. See
Section 8: Metering, Monitoring, and Report-
ing
of the product-specific instruction manual for more information on the
specific metering options available in a specific relay.
View Metering Using QuickSet
Use the procedures in the following steps to examine the relay metering with the
QuickSet HMI.
This example assumes that you have successfully established communication
with the relay (see
Making an EIA-232 Serial Port Connection on page 3.4
). In
addition, you must be familiar with relay access levels and passwords (see
Changing the Default Passwords in the Terminal on page 3.10
to change the
default access level passwords). You should also be familiar with QuickSet (see
Checking Relay Status in QuickSet on page 3.12
and
Step 1. Start QuickSet and establish a connection with the relay. See Step 1
and Step 2 of
Checking Relay Status in QuickSet on page 3.12
for
details on how to do this.
Step 2. Set the relay to a nominal operation mode. Perform the initial Global
Making Initial Global Settings in QuickSet on
to set the relay for 60-Hz operation, ABC phase rotation.
=>>
MET <Enter>
Relay 1 Date: 02/26/2015 Time: 01:35:05.221
Station A Serial Number: 0000000000
Phase Currents
IA IB IC
I MAG (A) 398.882 399.041 398.784
I ANG (DEG) -1.18 -120.97 119.21
Phase Voltages Phase-Phase Voltages
VA VB VC VAB VBC VCA
V MAG (kV) 133.994 133.986 133.953 231.903 231.815 232.450
V ANG (DEG) -0.17 -120.02 120.18 29.91 -89.92 150.01
Sequence Currents (A) Sequence Voltages (kV)
I1 3I2 3I0 V1 3V2 3V0
MAG 398.901 2.159 2.588 133.977 0.692 0.713
ANG (DEG) -0.98 -62.68 -115.80 0.00 -53.25 -120.79
A B C 3P
P (MW) 53.44 53.46 53.41 160.31
Q (MVAR) 0.95 0.89 0.91 2.75
S (MVA) 53.45 53.47 53.42 160.33
POWER FACTOR 1.00 1.00 1.00 1.00
LAG LAG LAG LAG
FREQ (Hz) 60.00 VDC1(V) 125.00 VDC2(V) 48.00
=>>
Figure 3.29
Terminal Screen MET Metering Quantities
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...