6.25
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Autoreclosing
Two-Circuit-Breaker Autoreclosing
Trip Logic and Reclose Sources for Single-Pole Breaker Applications
Internal Recloser
Program the recloser function to drive the trip logic with Relay Word bits R3PTE
(Recloser Three-Pole Trip Enable), R3PTE1 (Circuit Breaker BK1 Recloser
Three-Pole Trip Enable) and R3PTE2 (Circuit Breaker BK2 Recloser Three-Pole
Trip Enable) as follows:
E3PT :=
R3PTE
Three-Pole Trip Enable (SEL
OGIC
Equation)
E3PT1 :=
R3PTE1
Breaker 1 Three-Pole Trip (SEL
OGIC
Equation)
E3PT2 :=
R3PTE2
Breaker 2 Three-Pole Trip (SEL
OGIC
Equation)
These settings connect the internal recloser for both three-pole reclosing and sin-
gle-pole reclosing.
Enter enable settings ESPR1 and E3PR1 as appropriate for your application. By
default, the relay is a single-pole tripping relay; that is, if E3PT is logical 0 and
E3PT1 equals logical 0, the relay can single-pole trip Circuit Breaker BK1. If
E3PT1 equals logical 1, the relay can only three-pole trip Circuit Breaker BK1.
The same conditions apply to setting E3PT2 and Circuit Breaker BK2.
summarizes the relay trip logic enable options.
Relay Word bits R3PTE1 and R3PTE2 both equal logical 1 for any of the follow-
ing conditions when Global setting NUMBK (Number of Breakers in Scheme) is
2 and SPLSHT (Single-Pole Last Shot) is asserted (see
➤
BK1TYP and BK2TYP equal 3 (Circuit Breaker 1 and Circuit
Breaker 2 Trip Type)
➤
NSPSHOT := N (Number of Single-Pole Reclosures)
Example 6.1
Conditional Three-Pole Tripping for Circuit Breaker BK2
Your system reclosing requirement is that Circuit Breaker BK2 always three-
pole trips, unless Circuit Breaker BK2 is the leader. (This occurs when Cir-
cuit Breaker BK1 is out of service.) Program SEL
OGIC
control equation
ESPR2 as follows:
ESPR2 :=
LEADBK2 AND BK1LO
Single-Pole Reclose Enable—BK2
(SEL
OGIC
Equation)
Table 6.23
Trip Logic Enable Options
Enable Condition
Circuit Breaker BK1
Circuit Breaker BK2
E3PT
E3PT1
E3PT2
Single-
Pole Trip
Three-
Pole Trip
Single-
Pole Trip
Three-Pole
Trip
0
0
0
x
x
0
0
1
x
x
0
1
0
x
x
0
1
1
x
x
1
0
0
x
x
1
0
1
x
x
1
1
0
x
x
1
1
1
x
x
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...