8.14
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Monitoring
Circuit Breaker Monitor
Example 8.7
Pole Scatter Settings
Use Circuit Breaker 1, a single-pole tripping circuit breaker, for this exam-
ple. This example uses control inputs IN301, IN302, and IN303 for the A-,
B-, and C-Phases, respectively; you can use any control inputs that are
appropriate for your installation.
The control voltage for this example is 125 Vdc. Control Inputs IN301–
IN303 are located on I/O Board #3. Connect the circuit breaker normally
open auxiliary circuit breaker (52A) contacts through station battery power
to IN301, IN302, and IN303.
Set the relay to respond to these inputs by using the QuickSet
Breaker Mon-
itor (SET M)
settings:
52AA1 :=
IN301
A-Phase Normally Open Control Input—BK1
(SEL
OGIC
Equation)
52AB1 :=
IN302
B-Phase Normally Open Control Input—BK1
(SEL
OGIC
Equation)
52AC1 :=
IN303
C-Phase Normally Open Control Input—BK1
(SEL
OGIC
Equation)
Connect external trip signals to IN201, IN202, and IN203, and external close
signals to IN204, IN205, and IN206 for the A-, B-, and C-Phases, respec-
tively. This example uses control inputs IN201–IN206; you can use any con-
trol inputs that are appropriate for your installation.
Set the pole scatter trip alarm time threshold (B1PSTRT) at 4 ms, the pole
scatter close alarm time threshold (B1PSCLT) at 6 ms, and the pole discrep-
ancy time delay (B1PDD) at 1400 ms. Use your company standard practices
to determine these settings for your application. For this example, enter the
following settings:
B1PSTRT :=
4
Pole Scatter Trip Alarm Threshold—BK1 (1–999 ms)
B1PSCLT :=
6
Pole Scatter Close Alarm Threshold—BK1 (1–999 ms)
B1PDD :=
1400
Pole Discrepancy Time Delay—BK1 (1–9999 ms)
EB1MON :=
Y
Breaker 1 Monitoring (Y, N)
BK1TYP :=
1
Breaker 1 Trip Type (Single Pole = 1, Three Pole = 3)
BM1TRPA :=
TPA1 OR IN201
Breaker Monitor A-Phase Trip—BK1
(SEL
OGIC
Equation)
BM1TRPB :=
TPB1 OR IN202
Breaker Monitor B-Phase Trip—BK1
(SEL
OGIC
Equation)
BM1TRPC :=
TPC1 OR IN203
Breaker Monitor C-Phase Trip—BK1
(SEL
OGIC
Equation)
BM1CLSA :=
BK1CL OR IN204
Breaker Monitor A-Phase Close—
BK1 (SEL
OGIC
Equation)
BM1CLSB :=
BK1CL OR IN205
Breaker Monitor B-Phase Close—
BK1 (SEL
OGIC
Equation)
BM1CLSC :=
BK1CL OR IN206
Breaker Monitor C-Phase Close—
BK1 (SEL
OGIC
Equation)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...