3.22
SEL-421 Relay
Instruction Manual
Date Code 20171021
Testing
Checking Relay Operation
Step 4. Upload the new settings to the SEL-421.
a. Click
File > Send
.
b. QuickSet prompts you for the settings class you want to send to
the relay, as shown in the
Group Select
dialog box of
c. Click the check box for
Group 1
.
d. Click
OK
.
QuickSet responds with a dialog box similar to the second dialog
box of
.
If you see no error message, the new settings are loaded in the
relay.
Step 5. Display the MBC2 Relay Word bit on the front-panel LCD screen.
a. Access the front-panel LCD
MAIN MENU
.
b. Highlight
RELAY ELEMENTS
and press
ENT
.
c. You will see a
RELAY ELEMENTS
screen with
SEARCH
highlighted
at the bottom of the screen.
d. Press
ENT
to go to the
ELEMENT SEARCH
submenu shown in
e. Use the navigation keys to highlight
M
and press
ENT
to enter
character in the text input field.
f.
Enter the
B
,
C
, and
2
characters in like manner.
g. Highlight
ACCEPT
and press
ENT
.
The relay displays the LCD screen containing the MBC2
element, as shown in
.
Step 6. Set the magnitudes and angles of the test signals for a B-Phase-to-
C-phase fault.
a. Connect the test sources (with power off) to the relay, as in
This connection is a B-Phase-to-C-Phase fault where I
A
0 and
I
B
= –I
C
.
b. Adjust the voltage sources to provide the following test voltages:
V
A
= 67 V
0°, V
B
= 46.8 V
–150°, and V
C
= 46.8 V
150°.
c. Set the current source for I
B
= 0.0 A
–174°.
Figure 3.19
RELAY ELEMENTS LCD Screen Containing Element MBC2
PRESS to search
RELAY ELEMENTS
SEARCH
ROW 8
ROW 9
* =0 * =0
MCA2 =0 MCA4 =0
MBC2 =0 MBC4 =0
MAB2 =0 MAB4 =0
* =0 * =0
MCA1 =0 MCA3 =0
MBC1 =0 MBC3 =0
MAB1 =0 MAB3 =0
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...