7.4
SEL-421 Relay
Instruction Manual
Date Code 20171021
Metering, Monitoring, and Reporting
Metering
where the current
lags
the applied voltage. Conversely, Q is negative when the
voltage angle is less than the current angle (
V
<
I
); this is when the current
leads
the voltage, as in the case of capacitive loads.
The SEL-421 includes Relay Word bits to indicate the leading or lagging power
factor (see
). In the case of a unity power factor or
loss of phase or potential condition, the resulting power factor angle will be on
the axis of the complex power (P/Q) plane shown in
. This causes the
power factor Relay Word bits to rapidly change state (chatter). Be aware of
expected system conditions when monitoring the power factor Relay Word bits.
SEL does not recommend the use of chattering Relay Word bits in the SER or
anything that will trigger an event.
Figure 7.1
Complex Power (P/Q) Plane
Table 7.3
Instantaneous Metering Quantities—Power (Sheet 1 of 2)
Metered Quantity
Symbol
Fundamental
(50 Hz/
60 Hz Only)
RMS
(Harmonics
Included)
Per-phase fundamental real power
P
1
X
Per-phase true real power
P
rms
X
Per-phase reactive power
Q
1
X
X
Per-phase fundamental apparent power
S
1
X
Per-phase true apparent power
U
rms
X
Three-phase fundamental real power
3P
1
X
Three-phase true real power
3P
rms
X
Three-phase reactive power
3Q
1
X
X
Three-phase fundamental apparent power
3S
1
X
Q
P
+P
+Q
Comp
lex
Pow
er
S
1
Com
plex
Powe
r S
2
pf = Lead
pf = Lag
—P
+Q
+P
—Q
—P
—Q
Export power and
export reactive power
(inductive load)
Export power and
import reactive power
(capacitive load)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...