2.5
Date Code 20171021
Instruction Manual
SEL-421 Relay
Installation
Shared Configuration Attributes
Secondary Circuits
The SEL-421 is a very low burden load on the CT secondaries and PT secondar-
ies. For both the CT and PT inputs, the frequency range is 40–65 Hz.
The relay accepts two sets of three-phase currents from power system CT inputs:
➤
IAW, IBW, and ICW
➤
IAX, IBX, and ICX
For 5 A relays, the rated nominal input current, I
NOM
, is 5 A. For 1 A relays, the
rated nominal input current, I
NOM
, is 1 A.
Input current for both relay types can range to 20 • I
NOM
.
AC Current Inputs (Secondary Circuits) on page 1.14
for complete CT input
specifications.
The relay also accepts two sets of three-phase, four-wire (wye) potentials from
power system PT or CCVT (coupling-capacitor voltage transformer) secondaries:
➤
VAY, VBY, and VCY
➤
VAZ, VBZ, and VCZ
The nominal line-to-neutral input voltage for the PT inputs is 67 volts with a
range of 0–300 volts. The PT burden is less than 0.5 VA at 67 volts, L-N. See
for complete PT input specifications.
Some applications do not use all three phases of a source; for example, voltage
synchronization sources can be single phase. See
Section 6: Protection Applica-
for examples of connections to the potential inputs.
Secondary Circuit Connections on page 2.34
for information on connecting
power system secondary circuits to these inputs.
Relays that use the TiDL system do not contain secondary circuits on the relay.
The secondary circuit uses a remote SEL-2240 Axion to supply the voltages and
currents through a direct fiber link; however, the nominal current must be
selected to appropriately apply scaling through various protection functions. The
relay, by default, assumes 5 A as the nominal current selection. For 1 A scaling,
use the
CFG CTNOM
command (see
Table 14.28 on page 14.10 in the SEL-400
Series Relays Instruction Manual
for more information). The SEL-2245-42 AC
(In a vertical-mount relay, the right rear side is at the top.)
Figure 2.3
Rear 3U Template, Connectorized Analog Inputs
WARNING
Before working on a CT circuit, first
apply a short to the secondary wind-
ing of the CT.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...