6.84
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
345 kV Tapped Overhead Transmission Line Example
E50G
Residual Ground Inst./Def.-Time O/C Elements (N, 1–4)
3
E50Q
Negative-Sequence Inst./Def.-Time O/C Elements (N, 1–4)
N
E51S
Selectable Inverse-Time O/C Elements (N, 1–3)
1
E32
Directional Control (Y, AUTO, AUTO2)
AUTO2
ECOMM
Communications-Assisted Tripping (N, DCB, POTT, POTT2, POTT3,
DCUB1, DCUB2)
DCB
EBFL1
Breaker 1 Failure Logic (N, 1, 2, Y1, Y2)
N
E25BK1
Synchronism Check for Breaker 1 (Y, N, Y1, Y2)
N
E79
Reclosing (Y, Y1, N)
N
EMANCL
Manual Closing (Y, N)
N
ELOP
Loss-of-Potential (Y, Y1, N)
Y1
EDEM
Demand Metering (N, THM, ROL)
N
EADVS
Advanced Settings (Y, N)
N
Mho Phase-Distance Element Reach (Group)
Z1MP
Zone 1 Reach (OFF, 0.05–64
secondary)
3.20
Z2MP
Zone 2 Reach (OFF, 0.05–64
secondary)
11.00
Z3MP
Zone 3 Reach (OFF, 0.05–64
secondary)
50.5
Mho Phase-Distance Element Time Delay (Group)
Z1PD
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z2PD
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z3PD
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
OFF
Mho Ground-Distance Element Reach (Group)
Z1MG
Zone 1 (OFF, 0.05–64
secondary)
3.20
Z2MG
Zone 2 (OFF, 0.05–64
secondary)
11.00
Z3MG
Zone 3 (OFF, 0.05–64
secondary)
50.5
Zero-Sequence Current Compensation Factor (Group)
k0M1
Zone 1 ZSC Factor Magnitude (AUTO, 0.000–10)
0.750
k0A1
Zone 1 ZSC Factor Angle (–180.00 to +180 degrees)
–16.87
Ground-Distance Element Time Delay (Group)
Z1GD
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z2GD
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z3GD
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
OFF
Distance Element Common Time Delay (Group)
Z1D
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
0.000
Z2D
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
20.000
Z3D
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
0.000
SOTF Scheme (Group)
ESPSTF
Single-Pole Switch-Onto-Fault (Y, N)
N
EVRST
Switch-Onto-Fault Voltage Reset (Y, N)
Y
VRSTPU
Switch-Onto-Fault Reset Voltage (0.60–1.00 pu)
0.60–1.00 pu
52AEND
52A Pole Open Time Delay (OFF, 0.000–16000 cycles)
OFF
Table 6.21
Settings for 345 kV Tapped TX Example (Sheet 2 of 4)
Setting
Prompt
Entry
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...