12.23
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Settings
Report Settings
NOTE:
This category is only available
in relays that support 87L
communications.
Report Settings
The SER Points category is a freeform category for listing points to record in the
SER. Each point can be given a reporting name, a set state name, and a clear state
name. You can also indicate whether or not to make this point visible as an alarm
point on the front-panel LCD. The syntax for entry is:
Relay Word Bit Label, "Reporting Name", "Set State Name", "Clear State
Name", HMI Alarm Indication
Each of the names may consist of any printable ASCII character. The HMI alarm
condition is a Y/N choice. By default, there are no SER points configured.
The signal profile settings category consists of a freeform block for selecting ana-
log quantities to include in the signal profile followed by the settings described in
. Any of the analog quantities listed in
Section 12:Analog Quantities
in the product-specific instruction manual may be selected. As many as 20 analog
quantities can be included in the signal profile.
Table 12.37
87L Communications Bits
Label
a, b
a
x
= 1–4. These settings are hidden when E87CH = N or 2E or 3E or 4E. Also hidden if there is no
serial communications card installed.
b
nn
= 01–32. These settings are visible when E87CH = 2E, 3E, or 4E, and are hidden in all other cases.
Prompt
Default Value
87T
x
P1
•
NA
87T
x
P2
•
NA
87T
nn
E
•
NA
Table 12.38
Report Settings Categories
Settings
Reference
SER Chatter Criteria
SER Points
Signal Profile
Event Reporting
HIF Event Reporting
Event Reporting Analog Quantities
Event Reporting Digital Elements
Table 12.39
SER Chatter Criteria
Label
Prompt
Default Value
ESERDEL
Automatic Removal of Chattering SER Points (Y, N)
N
SRDLCNT
a
a
Setting is only available if ESERDEL := Y.
Number of Counts Before Auto-Removal (2–20)
5
SRDLTIM
Time for Auto-Removal (0.1–30 seconds)
1.0
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...