6.15
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
230 kV Overhead Distribution Line Example
Example Completed
This completes the application example describing configuration of the SEL-421
for step-distance protection of a 230 kV overhead transmission line. You can use
this example as a guide when setting the relay for similar applications. Analyze
your particular power system so you can properly determine your corresponding
settings.
Relay Settings
lists the protective relay settings for this example. Settings used in this
example appear in boldface type.
Table 6.6
Settings for 230 kV Overhead TX Example (Sheet 1 of 4)
Setting
Prompt
Entry
General Global (Global)
SID
Station Identifier (40 characters)
HARVARD -
230 kV
RID
Relay Identifier (40 characters)
SEL-421 Relay
NUMBK
Number of Breakers in Scheme (1, 2)
1
BID1
Breaker 1 Identifier (40 characters)
Circuit Breaker 1
NFREQ
Nominal System Frequency (Hz)
60
PHROT
System Phase Rotation (ABC, ACB)
ABC
DATE_F
Date Format (MDY, YMD, DMY)
MDY
FAULT
Fault Condition Equation (SEL
OGIC
Equation)
50P1 OR 51S1
OR Z2P OR Z2G
OR Z3P OR Z3G
Current and Voltage Source Selection (Global)
ESS
Current and Voltage Source Selection (Y, N, 1, 2, 3, 4)
N
Breaker Configuration (Breaker Monitoring)
EB1MON
Breaker 1 Monitoring (Y, N)
N
BK1TYP
Breaker 1 Trip Type (Single Pole = 1, Three Pole = 3)
3
Breaker 1 Inputs (Breaker Monitoring)
52AA1
A-Phase N/O Contact Input—BK1 (SEL
OGIC
Equation)
IN101
Line Configuration Settings (Group)
CTRW
Current Transformer Ratio—Input W (1–50000)
100
CTRX
Current Transformer Ratio—Input X (1–50000)
200
PTRY
Potential Transformer Ratio—Input Y (1–10000)
2000.0
VNOMY
Pt Nominal Voltage (L-L)—Input Y (60–300 V secondary)
115
PTRZ
Potential Transformer Ratio—Input Z (1–10000)
2000.0
VNOMZ
PT Nominal Voltage (L-L)—Input Z (60–300 V secondary) 115
Z1MAG
Positive-Sequence Line Impedance Magnitude
(0.05–255
secondary)
1.95
Z1ANG
Positive-Sequence Line Impedance Angle (5.00–90 degrees)
84.00
Z0MAG
Zero-Sequence Line Impedance Magnitude
(0.05–255
secondary)
6.20
Z0ANG
Zero-Sequence Line Impedance Angle (5.00–90 degrees)
81.50
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...