8.28
SEL-421 Relay
Instruction Manual
Date Code 20171021
Settings
Group Settings
Make
settings if Group setting ECOMM := DCB.
Make
settings if Group settings EBFL1 := 1, 2, Y1, or Y2; or
EBFL2 := 1, 2, Y1, or Y2.
Table 8.69
DCB Trip Scheme
Setting
Prompt
Default
Value
Increment
Z3XPU
Zone 3 Reverse Pickup Time Delay (0.000–16000 cycles)
1.000
0.125
Z3XD
Zone 3 Reverse Dropout Delay (0.000–16000 cycles)
6.000
0.125
BTXD
Block Trip Receive Extension Time (0.000–16000 cycles)
1.000
0.125
21SD
Zone 2 Distance Short Delay (0.000–16000 cycles)
2.000
0.125
67SD
Level 2 Overcurrent Short Delay (0.000–16000 cycles)
2.000
0.125
BT
Block Trip Received (SEL
OGIC
Equation)
NA
Table 8.70
Breaker 1 Failure Logic (and Breaker 2 Failure Logic
a
) (Sheet 1 of 2)
Setting
Prompt
Default Value
Increment
5 A
1 A
50FP1
Phase Fault Current Pickup—BK1
(0.50–50 A secondary) 5 A
(0.10–10 A secondary) 1 A
6.00
1.20
0.01
BFPU1
Breaker Failure Time Delay—BK1 (0.000–6000 cycles)
9.000
9.000
0.125
SPBFPU1
b
SPT Breaker Fail. Time Delay—BK1 (0.000–6000 cycles)
6.000
6.000
0.125
RTPU1
Retrip Time Delay—BK1 (0.000–6000 cycles)
3.000
3.000
0.125
RT3PPU1
Three-Pole Retrip Time Delay—BK1 (0.000–6000 cycles)
3.000
3.000
0.125
BFI3P1
Three-Pole Breaker Failure Initiate—BK1 (SEL
OGIC
Equation)
NA
NA
BFIA1
A-Phase Breaker Failure Initiate—BK1 (SEL
OGIC
Equation)
NA
NA
BFIB1
B-Phase Breaker Failure Initiate—BK1 (SEL
OGIC
Equation)
NA
NA
BFIC1
C-Phase Breaker Failure Initiate—BK1 (SEL
OGIC
Equation)
NA
NA
BFIDO1
Breaker Fail Initiate Dropout Delay—BK1 (0.000–1000 cycles)
1.500
1.500
0.125
BFISP1
Brkr Fail Init Seal-in Delay—BK1 (0.000–1000 cycles)
2.000
2.000
0.125
ENCBF1
No Current/Residual Current Logic—BK1 (Y, N)
N
N
50RP1
Residual Current Pickup—BK1
(0.25–50 A secondary) 5 A
(0.05–10 A secondary) 1 A
1.00
0.20
0.01
NPU1
No Current Brkr Fail. Delay—BK1 (0.000–6000 cycles)
12.000
12.000
0.125
BFIN1
No Current Breaker Failure Initiate—BK1 (SEL
OGIC
Equation)
NA
NA
ELCBF1
Load Current Breaker Failure Logic—BK1 (Y, N)
N
N
50LP1
Phase Load Current Pickup—BK
(0.25–50 A secondary) 5 A
(0.05–10 A secondary) 1 A
0.50
0.10
0.01
LCPU1
Load Pickup Time Delay—BK1 (0.000–6000 cycles)
9.000
9.000
0.125
BFILC1
Breaker Failure Load Current Initiate—BK1 (SEL
OGIC
Equation)
NA
NA
EFOBF1
Flashover Breaker Failure Logic—BK1 (Y, N)
N
N
50FO1
Flashover Current Pickup—BK1
(0.25–50 A secondary) 5 A
(0.05–10 A secondary) 1 A
0.50
0.10
0.01
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...