![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 166](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726166.webp)
5.6
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Functions
Current and Voltage Source Selection
➤
Series-compensation line logic
➤
Load-encroachment logic
➤
OOS (out-of-step) logic
➤
Distance elements
➤
Instantaneous line overcurrent elements
➤
Inverse-time overcurrent elements
➤
DCUB (directional comparison unblocking) trip scheme logic
➤
, except synchrophasors
Breaker current-source settings (BK1I and BK2I) identify the currents used in the
following elements/features described in later in this section and in other sec-
tions:
➤
Open-phase detection logic
➤
Inverse-time overcurrent elements
➤
Circuit breaker failure protection
➤
Circuit Breaker Monitor on page 7.7
➤
Polarizing current-source setting IPOL identifies the single current input con-
nected to a zero-sequence current source (e.g., transformer bank neutral). This
zero-sequence current is used as a reference in the zero-sequence current-polar-
ized directional element. Such a directional element is applied to ground overcur-
rent elements (see
). Setting IPOL is not used often and
thus is usually set to NA. Notice that in
there
are relatively few scenarios where setting IPOL can be set to a current channel
selection (only those cases where three-phase current input IX is not used for any
other function). An example of using setting IPOL is found later in this subsec-
tion.
Voltage Source Switching and Uses
Refer to the global settings in
. Alternate voltage source
switching between VY and VZ in
is more straightforward (as shown in
) than the preceding discussion on current-source selection/switching
(compare to
through
).
Table 5.4
Available Voltage Source Selection Setting Combinations
a
(Sheet 1 of 2)
NUMBK (number of
breakers)
ESS
(source selection)
Line Voltage Source
ALINEV (alternate
line voltage source)
1
Y
VY
VZ or NA
1
N
VY
NA
1
1
VY
VZ or NA
1
2
VY
VZ or NA
1
3
not allowed
1
4
not allowed
2
Y
VY
VZ or NA
2
N
VY
NA
2
1
not allowed
2
2
not allowed
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...