6.41
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
DTA :=
RMB3A
.
Direct Transfer Trip A-Phase (SEL
OGIC
Equation)
DTB :=
RMB4A
.
Direct Transfer Trip B-Phase (SEL
OGIC
Equation)
DTC :=
RMB5A
.
Direct Transfer Trip C-Phase (SEL
OGIC
Equation)
Trip Unlatch Options
Unlatch the control output programmed for tripping after the circuit breaker aux-
iliary a contacts break the dc current. The SEL-421 provides three methods for
unlatching control outputs programmed for tripping after occurrence of a protec-
tion trip:
➤
ULTR—following a protection trip, all three poles
➤
TOPD—Unlatch single-pole trip if another protection trip occurs
during single-pole dead time
➤
TULO—following a protection trip, phase selective
ULTR
Use ULTR, the unlatch trip SEL
OGIC
control equation, to unlatch all three poles.
Use the default setting, to assert ULTR when you push the front-panel
TARGET
RESET
pushbutton.
ULTR :=
TRGTR
.
Unlatch Trip (SEL
OGIC
Equation)
TOPD
It is common practice to trip the two remaining phases after the single-pole open
dead time, or if the single-pole autoreclose cycle does not reset, following the
original single-pole trip. If the SEL-421 internal reclosing relay is being used, the
E3PT, E3PT1, and E3PT2 settings in the trip logic should be set as shown in
and
Internal Recloser on page 6.25 in the SEL-400
Series Relays Instruction Manual
. See
Autoreclose Example on page 6.137
for
information on using the SEL-421 reclosing relay.
To illustrate another way of using an external reclosing relay, this example will
not use the SEL-421 Relay’s autoreclose logic, rather, it uses the TOP (Trip
During Open Pole) Relay Word bit to control the trip logic.
The timer setting TOPD determines the length of time for converting any subse-
quent single-pole trips to a three-pole trip following the original single-pole trip.
Set this timer to the single-pole open dead time (30 cycles) and the reset time
(three seconds) for the recloser plus a 5-cycle safety margin. See
Open-Pole Time Delay on page 5.139
in this manual and
External Recloser on page 6.26 in the SEL-400 Series Relays
Instruction Manual
for additional information.
TOPD :=
215.00
.
Trip During Open Pole Time Delay (2.000–8000 cycles)
TULO
Use TULO (Trip Unlatch Option) to select the conditions that cause the SEL-421
to unlatch the control outputs that you programmed for tripping. You can select
from among the four trip unlatch options in
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...