10.8
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Testing, Troubleshooting, and Maintenance
Test Methods
Example: Testing the 50P1 Element With a Control Output
This procedure shows how to set control output OUT105 to test the SEL-451
50P1 Phase Instantaneous Overcurrent element.
For this test, you must have a computer with QuickSet for the relay, a variable
current source for relay testing, and a control output closure indicating device
such as a test set or a VOM (volt ohmmeter).
In this example, use QuickSet to configure the relay. You must have a computer
that is communicating with the relay and running QuickSet (see
Changes in Initial Global Settings on page 3.20
).
Step 1. Prepare to control the relay with QuickSet by establishing communi-
cation, checking passwords, and reading relay settings.
Step 2. Click the
Outputs > Main Board
branch of the QuickSet
Settings
tree structure to view output settings (shown in
).
The
Main Board Outputs
dialog box appears.
Step 3. Set OUT105 to respond to the 50P1 element pickup.
a. Move the cursor to the OUT105 Main Board Output105
(SEL
OGIC
) text box and double-click the left (regular) mouse
button.
b. Delete the NA default setting.
c. Type 50P1.
d. Press
<Tab>
or click in any other text box.
Figure 10.2
Setting Main Board Outputs: QuickSet
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...