3.12
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Basic Relay Operations
Checking Relay Status
Checking Relay Status Using the Terminal
The procedure in the following steps assumes that you have successfully estab-
lished communication with the relay (see
Making an EIA-232 Serial Port Con-
). In addition, you must be familiar with relay access levels
and passwords (see
Changing the Default Passwords in the Terminal on
to change the default access level passwords).
Step 1. Enter Access Level 1.
a. Using a communications terminal, type
ACC <Enter>
.
b. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1 => prompt.
Step 2. Type
STA <Enter>
. The relay returns a status terminal screen simi-
lar to that in
Step 3. Type
STA A <Enter>
to view all relay status entries.
For more information on relay status report items, see
.
Checking Relay Status in QuickSet
You can use QuickSet to check relay status. Use the
HMI > Meter Control
menu to view status conditions.
The procedure in the following steps assumes that you have successfully estab-
lished communication with the relay (see
Making an EIA-232 Serial Port Con-
). In addition, you must be familiar with relay access levels
and passwords (see
Changing the Default Passwords in the Terminal on
to change the default access level passwords). You should also be
familiar with QuickSet (see
Step 1. Configure the communications port.
a. Start QuickSet.
NOTE:
The DTR parameter has no
effect on communications with the
relay.
b. On the top toolbar, click
Communications > Parameters
.
You will see the
Communication Parameters
dialog box
.
=>
STA <Enter>
Relay 1 Date: mm/dd/yyyy
Time:07:02:50.776
Station A Serial Number: 000000000
FID=SEL-451-1-Rxxx-V0-Zxxxxxx-Dyyyymmdd CID=0x9aed
Failures
No Failures
Warnings
No Warnings
SELogic Relay Programming Environment Errors
No Errors
Relay Enabled
=>
Figure 3.7
Relay Status
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...