7.11
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Metering
Battery Metering
NOTE:
Not all SEL-400 series relays
support synchrophasor
measurements.
When you issue the
MET PM
time
command, the relay captures the time-syn-
chronized data for the given trigger time (specify
time
in 24-hour format). The
relay displays the synchrophasor data immediately after the time trigger.
The synchrophasor measurements are only valid when a suitable high-accuracy
IRIG-B or PTP time source is connected to the relay, as indicated by Relay Word
bit TSOK = logical 1.
The
MET PM
command is only available when the relay is configured for phasor
measurement functions (Global settings) and the relay is in high-accuracy time-
keeping mode.
Battery Metering
The relay monitors battery system voltages and records time stamps for voltage
excursions. In addition, the relay records maximum and minimum battery volt-
ages.
shows a sample dc battery monitor meter report. Use the
MET
BAT
command from a communications terminal to obtain this report.
Any battery voltage between setting DCLWP and the dc battery monitor low
limit of 15 Vdc is in the L-Zone. Battery voltages in the H-Zone are voltages
higher than the DCHWP setting.
Use the
MET RBM
command from a communications terminal to reset the dc
battery monitor. You can program a SEL
OGIC
control equation RST_BAT (in
Monitor settings) to control dc battery monitor reset.
=>>
MET BAT <Enter>
Relay 1 Date: 06/07/2008 Time: 22:51:47.067
Station A Serial Number: 2008030645
Station Battery VDC VDCPO VDCNE VAC
VDC1 (V) 115.86 57.32 -58.54 0.01
VDC1(V) Date Time
Minimum 105.86 04/07/2008 22:43:04.022
Enter L-Zone 04/07/2008 22:40:14.162
Exit L-Zone 04/07/2008 22:44:09.223
Maximum 125.86 04/09/2008 12:34:14.321
Enter H-Zone 04/09/2008 12:31:32.543
Exit H-Zone 04/09/2008 12:35:12.657
LAST DC RESET: 01/15/2008 20:10:31.427
=>>
Figure 7.6
Battery Metering: Terminal
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...