7.7
Date Code 20171021
Instruction Manual
SEL-421 Relay
Metering, Monitoring, and Reporting
Circuit Breaker Monitor
Synchrophasor Metering
The SEL-421 provides synchrophasor measurement with an angle reference
according to IEEE C37.118. See
Section 7: Metering in the SEL-400 Series
Relays Instruction Manual
for details of synchrophasor metering.
Circuit Breaker Monitor
The SEL-421 features advanced circuit breaker monitoring. The general features
of the circuit breaker monitor are described in
page 8.1 in the SEL-400 Series Relays Instruction Manual
. The SEL-421 sup-
ports monitoring of two breakers, designated 1 and 2.
Station DC Battery System Monitor
The SEL-421 automatically monitors station battery system health by measuring
the dc voltage, ac ripple, and voltage between each battery terminal and ground.
The relay provides two dc monitor channels, Vdc1 and Vdc2. See
Battery System Monitor on page 7.7 in the SEL-400 Series Relays Instruction
Manual
for a complete description of the battery monitor.
Reporting
The SEL-421 features comprehensive power system data analysis capabilities,
which are described in
Section 9: Reporting in the SEL-400 Series Relays
Instruction Manual
. This section describes reporting characteristics that are
unique to the SEL-421.
Duration of Data Captures and Event Reports
The SEL-421 stores high-resolution raw data and filtered data. The number of
stored high-resolution raw data captures and event reports is a function of the
quantity of data contained in each capture.
lists the maximum number of data captures/event reports the relay
stores in nonvolatile memory when ERDIG = S for various report lengths and
sample rates. The relay automatically overwrites the oldest events with the new-
est events when the nonvolatile storage capacity is exceeded.
NOTE:
Consider the total capture
time when choosing a value for
setting LER at the SRATE := 8 kHz. At
LER := 3.0 the relay records at least 13
data captures when ERDIG = S. These
and smaller LER settings are sufficient
for most power system disturbances.
The relay stores high-resolution raw and filtered event data in nonvolatile mem-
ory.
lists the storage capability of the SEL-421 for common event
reports.
show the number of event reports the relay stores at
the maximum data capture times for each SRATE sampling rate setting. Table
entries are the maximum number of stored events; these can vary by 10 percent
according to relay memory usage.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...