Instruction Manual
SEL-400 Series Relays
ASCII Command Reference
Command Description
LOOPBACK
Use the
LOOPBACK
command to instruct the relay to receive the transmitted
M
IRRORED
B
ITS
communications data on the same serial port. See
for more information on M
IRRORED
B
ITS
communications.
LOOP
The
LOOP
command puts the relay serial port in loopback if you have previ-
ously configured the port for M
IRRORED
B
ITS
communications. If you have
enabled both of the M
IRRORED
B
ITS
communications channels (A and B), then
you must specify the channel parameter. If you have only one of the channels
enabled, then the relay assumes that channel if you do not specify that channel in
the command. If you do not specify a time-out period, the relay provides a 5-min-
ute time-out.
You can enter the options in any order. If you operate the relay using both M
IR
-
RORED
B
ITS
communications channels (A and B), then you must specify the
channel parameter by using the
LOOP A
command and the
LOOP B
command.
When you issue the
LOOP
command, the relay responds with statements about
the loopback time, status of the RMB (Receive M
IRRORED
B
ITS
), and
Are you
sure (Y/N)?
. If you answer
Y <Enter>
, the relay responds with
Loopback Mode
Started
.
In the loopback mode, ROK drops out and the relay uses LBOK to indicate
whether the data transmissions are satisfactory. The relay collects COM data as
usual. Time synchronization and virtual terminal modes are not available during
loopback. The relay continues passing analog quantities.
Table 14.80
LOOP Command
Command
Description
Access Level
LOOP
Begin loopback of a single enabled M
IRRORED
B
ITS
commu-
nications channel (either Channel A or Channel B) for 5 minutes;
ignore input data and force receive bits (RMB) to defaults.
P, A, O, 2
LOOP
c
a
a
Parameter
c
is A or B, representing Channel A or Channel B.
Begin loopback of M
IRRORED
B
ITS
communications
Channel
c
for 5 minutes; ignore input data and force receive
bits (RMB) to defaults.
P, A, O, 2
LOOP
t
Begin loopback of a single M
IRRORED
B
ITS
communications
channel (either Channel A or Channel B) and end the loop-
back after time-out
t
minutes; ignore input data and force
receive bits (RMB) to defaults;
t
range is 1–5000 minutes.
P, A, O, 2
LOOP
t c
Begin loopback of a single M
IRRORED
B
ITS
communications
channel (either Channel A or Channel B) and end the loop-
back after time-out t minutes; ignore input data and force
receive bits (RMB) to defaults;
t
range is 1–5000 minutes.
P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...