5.163
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Functions
Synchronism Check
For a single-circuit breaker application, you can use either bus-side potentials or
line-side potentials for line relaying; connect the three-phase voltage source to
potential inputs VAY, VBY, and VCY. If a single-phase voltage source is avail-
able on the other side of the circuit breaker for synchronism check, connect the
source to potential input VAZ, VBZ, or VCZ.
Voltage Magnitude and Angle Compensation
The
example continues in
example
demonstrates possible voltage input connections (presuming ABC phase rota-
tion). The synchronism-check voltage reference (V
P
) is from the A-Phase voltage
(V
A
) of the line. You can connect phase-to-phase voltage V
BC
originating from
Bus 1, and connect phase-to-neutral voltage V
C
from Bus 2. Thus, Bus 1 voltage
V
BC
lags synchronism-check voltage reference V
P
by 90 degrees, and Bus 2 volt-
age V
C
lags the synchronism-check voltage reference V
P
by 240 degrees. To
compensate for these steady-state angle differences, set KS1A for Bus 1 and
KS2A for Bus 2.
KS1A :=
90
.
Synchronism Source 1 Angle Shift (0, 30, …, 330 degrees)
KS2A :=
240
.
Synchronism Source 2 Angle Shift (0, 30, …, 330 degrees)
Figure 5.122
Example Synchronism-Check Voltage Connections to the SEL-421
Bus 2
Bus 1
Relay rear panel
(partial)
Three-phase line
voltage connections
Separate, single-phase
bus/source
voltage connections
Line
BK2
BK1
VAY VBY VCY
VAZ VBZ VCZ
1
3
1
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...