6.17
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
230 kV Overhead Distribution Line Example
Distance Element Common Time Delay (Group)
Z1D
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
0.000
Z2D
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
20.000
SOTF Scheme Settings (Group)
ESPSTF
Single Pole Switch-Onto-Fault (Y, N)
N
EVRST
Switch-Onto-Fault Voltage Reset (Y, N)
Y
VRSTPU
Switch-Onto-Fault Reset Voltage (0.60–1.00 pu)
0.8
52AEND
52A Pole Open Delay (OFF, 0.000–16000 cycles)
OFF
CLOEND
CLSMON or Single Pole Delay (OFF, 0.000–16000 cycles) 10.000
SOTFD
Switch-Onto-Fault Enable Duration (0.500–16000 cycles)
10.000
CLSMON
Close Signal Monitor (SEL
OGIC
Equation)
IN102
Phase Instantaneous Overcurrent Pickup Settings (Group)
50P1P
Level 1 Pickup (OFF, 0.25–100 A secondary)
13.29
Phase Overcurrent Definite-Time Delay (Group)
67P1D
Level 1 Time Delay (0.000–16000 cycles)
0.000
Phase Overcurrent Torque Control (Group)
67P1TC
Level 1 Torque Control (SEL
OGIC
Equation)
1
Selectable Operating Quantity Time Overcurrent Element Settings (Group)
51S1O
51S1 Operating Quantity (IA
n
, IB
n
, IC
n
, IMAX
n
, I1L,
3I2L, 3I0
n
)
a
3I0L
51S1P
51S1 Overcurrent Pickup (0.25–16 A secondary)
1.72
51S1C
51S1 Inverse-Time Overcurrent Curve (U1–U5)
U3
51S1TD
51S1 Inverse-Time Overcurrent Time Dial (0.50–15.00)
1.96
51S1RS
51S1 Inverse-Time Overcurrent Electromechanical Reset (Y, N) Y
51S1TC
51S1 Torque Control (SEL
OGIC
Equation)
32GF
Directional Control (Group)
ORDER
Ground Directional Element Priority (combine Q, V, I)
QV
E32IV
Zero-Sequence Voltage And Current Enable
(SEL
OGIC
Equation)
1
Pole-Open Detection Settings (Group)
EPO
Pole-Open Detection (52, V)
52
SPOD
Single-Pole Open Dropout Delay (0.000–60 cycles)
0.500
3POD
Three-Pole Open Dropout Delay (0.000–60 cycles)
0.500
Trip Logic Settings (Group)
TR
Trip (SEL
OGIC
Equation)
Z1T OR Z2T OR
51S1T
TRSOTF
Switch-Onto-Fault Trip (SEL
OGIC
Equation)
Z2P OR Z2G OR
50P1
DTA
Direct Transfer Trip A-Phase (SEL
OGIC
Equation)
NA
DTB
Direct Transfer Trip B-Phase (SEL
OGIC
Equation)
NA
DTC
Direct Transfer Trip C-Phase (SEL
OGIC
Equation)
NA
BK1MTR
Manual Trip – Breaker 1 (SEL
OGIC
Equation)
OC1 OR
PB8_PUL
Table 6.6
Settings for 230 kV Overhead TX Example (Sheet 3 of 4)
Setting
Prompt
Entry
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...