3.12
SEL-421 Relay
Instruction Manual
Date Code 20171021
Testing
Checking Relay Operation
Step 4. Connect a test source to the relay.
a. Set the current output of a test source to zero output level.
b. Connect a single-phase current output of the test source to the
IAW analog input (see
Step 5. Increase the current source to produce a current magnitude greater
than 1.00 A secondary in the relay.
You will see that the 50Q1 element state changes on the LCD screen
from 50Q1 = 0 to 50Q1 = 1.
Negative-Sequence Directional Element for Phase Faults
The SEL-421 features a phase directional element (represented by Relay Word
bits F32P/R32P) to supervise the phase-distance elements and to control phase
directional elements. The negative-sequence directional element, F32Q/R32Q, is
a part of the phase directional element, F32P/R32P. Whenever the negative-
sequence directional element asserts, the phase directional element asserts.
The relay also contains a ground directional element, F32G/R32G, for directional
control of the ground-distance elements and ground overcurrent elements. For
more information on directional elements, see
, and
Section 6: Protection Applications Examples
.
The SEL-421 calculates the negative-sequence impedance Z2 from the magni-
tudes and angles of the negative-sequence voltage and current.
defines this function (the ‘c’ in Z2c indicates “calculated”).
Equation 3.1
Figure 3.10
RELAY ELEMENTS Screen Containing Element 50Q1
PRESS to search
RELAY ELEMENTS
SEARCH
ROW 26
ROW 27
67Q4 =0
* =0
67Q3 =0
* =0
67Q2 =0
* =0
67Q1 =0
* =0
50Q4 =0
67Q4T =0
50Q3 =0
67Q3T =0
50Q2 =0
67Q2T =0
50Q1 =0
67Q1T =0
where:
V2 = the negative-sequence voltage
I2 = the negative-sequence current
Z1ANG = the positive-sequence line impedance angle
Re = the real part of the term in brackets, for example, (Re[A + jB] = A)
* = the complex conjugate of the expression in parentheses,
(A + jB)* = (A – jB)
Z2c
Re V
2
1 Z1ANG I
2
I
2
2
------------------------------------------------------------------------
=
V
2
I
2
---------
V
2
Z1ANG
I
2
–
–
cos
=
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...