![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 1215](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_12167261215.webp)
14.9
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
ASCII Command Reference
Command Description
CEV NSUM
The
CEV NSUM
returns the Compressed ASCII event report with no event summary.
CEV S
x
Use the
CEV S
x
command to specify the sample data resolution of the Com-
pressed ASCII event report. The sample data resolution
x
can be 4, 8, or 12, depend-
ing on the relay; the default value is 4-samples/cycle if you do not specify
S
x
. The
S
x
option overrides the
L
option.
CEV TERSE
The
CEV TERSE
command returns a Compressed ASCII event report without
the event report labels.
Use the
TERSE
option with any of the
CEV
commands except
CEV ACK
.
Table 14.24
CEV NSUM Command
Command
Description
Access Level
CEV NSUM
Return the most recent event report without the event
summary at full length with 4-samples/cycle data in
Compressed ASCII format.
1, B, P, A, O, 2
CEV
n
a
NSUM
a
Parameter
n
indicates event order or serial number; see
Return a particular n event report without the event sum-
mary at full length with 4-samples/cycle data in Com-
pressed ASCII format.
1, B, P, A, O, 2
Table 14.25
CEV S
x
Command
Command
Description
Access Level
CEV S
x
Return the most recent event report at full length with
x
-samples/cycle data in Compressed ASCII format.
1, B, P, A, O, 2
CEV
n
a
S
x
a
Parameter
n
indicates event order or serial number: see
Return a particular n event report at full length with
x
-sam-
ples/cycle data in Compressed ASCII format.
1, B, P, A, O, 2
Table 14.26
CEV TERSE Command
Command
Description
Access Level
CEV TERSE
Return the most recent event report at full length with-
out the report labels with 4-samples/cycle data in
Compressed ASCII format.
1, B, P, A, O, 2
CEV
n
a
TERSE
a
Parameter
n
indicates event order or serial number.
Return a particular n event report at full length without
the report labels with 4-samples/cycle data in Com-
pressed ASCII format.
1, B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...