3.18
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Basic Relay Operations
Making Simple Settings Changes
Rename, or assign as many as 200 alias names to any Relay Word bit or analog
quantity in the relay. The maximum length of an alias is seven characters. Valid
characters are 0–9, A–Z (only uppercase), and _ (underscore), and must contain
at least one alphabetic character. Ensure that no Relay Word bit or analog quan-
tity appears more than once in the alias settings. Each alias name must be unique,
i.e., you cannot use the name of an existing Relay Word bit or analog quantity. If
you remove the alias name, all settings that referenced that alias revert to the
original name.
Use the
SHO T
command to view the default settings, as shown in
.
Making Text-Edit Mode Alias Changes
Assign the alias name THETA to math variable PMV01 and the alias TAN to
math variable PMV02. These variables are then used in calculating the tangent of
theta, using their alias names in the equation.
Step 1. Prepare to control the relay at Access Level 2.
a. Type
ACC <Enter>
at a communications terminal.
b. Type the Access Level 1 password and press
<Enter>
.
You will see the Access Level 1 => prompt.
c. Type
2AC <Enter>
.
d. Type the correct password to go to Access Level 2.
You will see the =>> prompt.
Step 2. Type
SET T <Enter>
to access the alias settings.
shows a representative computer terminal screen.
Step 3. Type
> <Enter>
for the relay to display the first line that you can
edit.
Step 4. Type
PMV01,THETA <Enter>
at the Line 2
?
settings prompt to set
the alias for PMV01.
The relay verifies that this is a valid entry, then responds with the
next line prompt
3:
followed by the
?
settings prompt.
Step 5. Type
PMV02,TAN <Enter>
at the Line 3
?
settings prompt to set
the alias for PMV02.
The relay verifies that this is a valid entry, then responds with the
next line prompt
4:
followed by the
?
settings prompt.
Step 6. Type
END <Enter>
to end the settings session.
The relay scrolls a readback of all the front-panel settings, eventually
displaying the
Save settings (Y, N) ?
prompt. At the end of the
readback information, just before the
Save settings (Y, N) ?
prompt, you can verify the new display point information.
Step 7. Type
Y <Enter>
to save the new settings.
=>>
SHO T <Enter>
Alias
Relay Aliases
(RW Bit or Analog Qty. 7 Character Alias [0-9 A-Z _])
1: EN,"RLY_EN"
=>>
Figure 3.12
Default Alias Settings
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...