5.8
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Control
Disconnect Logic
the 89CST
m
seal-in timer, you can ensure retention of the close signal until the
disconnect switch closes completely. If there is no complete disconnect switch
operation during the time 89ALP
m
defines, the relay asserts Relay Word bit
89AL
m
and reports that the disconnect switch is in an undetermined state.
The scenario in which both 89AM
m
and 89BM
m
are asserted simultaneously
would occur on a rare disconnect switch failure or a short-circuited auxiliary con-
tact wire connection. When this condition occurs for 89ALP
m
seconds, the
89AL
m
alarm status output will assert.
Disconnect Switch Close and Open Immobility Timer Logic
The Close and Open Immobility Timer Logic detects when a disconnect opera-
tion failed to initiate.
Close and Open Immobility Timer Logic Inputs
LOCAL
The LOCAL Relay Word bit supervises local disconnect control and is based on
the LOCAL SEL
OGIC
control equation in the Bay settings class. Disconnect
switch operations from the front panel are possible when the LOCAL Relay
Word bit is asserted, in other words, the LOCAL Relay Word bit prevents control
from the HMI without proper supervision.
89CBL
m
, 89OBL
m
The 89CBL
m
and 89OBL
m
SEL
OGIC
control equations provide an alternative
customizable method for blocking the initiation of a disconnect switch open or
close command, respectively.
Figure 5.4
Close Immobility Timer Logic
Close Immobility Timer
89CITm
60
CYC
89CIRm
(default setting:
NOT 89OPNm)
Relay
Word
Bits
* SEL
OGIC
control equation
89CIMm
(Reset)
89CBLm
89OPEm
89CCMm
89CCm (ASCII)
*89CCNm (k – 1/8 cyc.)
*89CCNm (k)
*LOCAL
Figure 5.5
Open Immobility Timer Logic
Open Immobility Timer
89OITm
60
CYC
89OIRm
(default setting:
NOT 89CLm)
Relay
Word
Bits
89OIMm
(Reset)
89OBLm
89CLSm
89OCMm
89OCm (ASCII)
*89OCNm (k – 1/8 cyc.)
*89OCNm (k)
*LOCAL
* SEL
OGIC
control equation
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...