Date Code 20171006
Instruction Manual
SEL-400 Series Relays
ASCII Command Reference
Command Description
TEST DB2 OFF
Use the
TEST DB2 OFF
command to end the CADI2 database testing session
and remove the override values. The relay returns the CADI2 database registers
to the pretest values.
3
When removing all existing digital override values, the relay responds,
Digital
Overrides Removed
. If no digital override is ever configured, the
Overrides Not
Found
message will be displayed. The analog override removal acknowledgment
messages are similar.
TEST FM
The
TEST FM
command overrides normal Fast Meter quantities for testing pur-
poses. You can override only “reported” Fast Meter values. For more information
on Fast Meter and the relay, see
SEL Fast Meter, Fast Operate, Fast SER Mes-
sages, and Fast Message Data Access on page 15.28
.
TEST FM
Values you enter in Fast Meter storage are “override values.” Use the
TEST FM
command to display override values and write override values in the Fast Meter
report.
When you display Fast Meter data overrides with the
TEST FM
command, the
relay shows the item label, and override values.
To force a value, use the
TEST FM
label value1 value2
command. The item
label
label
is any analog channel label in the Fast Meter configuration (if avail-
able), any digital element label (from the
DNA
command), and any status ele-
ment label (from the
BNA
command) except the TEST and FMTEST items.
Table 14.132
TEST DB2 OFF Command
Command
Description
Access Level
TEST DB2 D
OFF
Clear all digital override testing values from the CADI2
database.
B, P, A, O, 2
TEST DB2 D
name1
a
OFF
a
Digital
name1
can be any Relay Word bits or additional binary input points in DNP3 map.
Clear digital override testing value specified by name
name1
from the CADI2 database.
B, P, A, O, 2
TEST DB2 A
OFF
Clear all analog override testing values from the CADI2
database.
B, P, A, O, 2
TEST DB2 A
name2
b
OFF
b
See Section 12: Analog Quantities in the product-specific instruction manual for available analog
name2
.
Clear analog override testing value specified by name
name2
from the CADI2 database.
B, P, A, O, 2
Table 14.133
TEST FM Command
Command
Description
Access Level
TEST FM
Display present override values.
1, B, P, A, O, 2
TEST FM
label
value1 value2
Write new data
value1
and
value2
to the Fast Meter
report at the item label
label
. Parameter
value2
is optional.
B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...