3.61
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Basic Relay Operations
Operating the Relay Inputs and Outputs
Step 3. Prepare the relay to download the SER report.
a. Type
FILE READ REPORTS SER.TXT <Enter>
.
b. If you want the Compressed ASCII file, type the following:
FILE READ REPORTS CSER.TXT <Enter>
Step 4. Download the SER report. Perform the steps necessary for your ter-
minal emulation program to receive a file.
Typically, these are the file transfer steps:
NOTE:
Transferring SER files (or
CSER files) with the
FILE READ
REPORTS
SER.TXT
command, performs an
SER CV
command as part of the transfer. SER
CV clears the SER information from
the present port. With the SER
information cleared, there are no data
available for subsequent SER or CSER
transfers from the same port.
➢
Specify the destination file location in your computer file
storage system and file name.
➢
Select the transfer type as
YModem
(if not already enabled).
➢
Click
Receive
.
You will usually see a confirmation message when the file transfer is
complete.
Step 5. When the SER.txt file has transferred successfully, use a word-pro-
cessing program to view the contents of the file.
You will see the SER records in a format similar to
Operating the Relay Inputs and Outputs
SEL-400 series relays give you great ability to perform control actions at bay and
substation locations via the relay control outputs. The control outputs close and
open circuit breakers, switch disconnects, and operate auxiliary station equip-
ment such as fans and lights. The relay reads data from the power system and
interfaces with external signals (contact closures and data) through the control
inputs. This subsection is an introduction to operating the control outputs and
control inputs. For more information on connecting and applying the control out-
puts and control inputs, see
Section 2: Installation
in the product-specific instruc-
tion manual.
Control Output
The relay features standard, hybrid (high-current interrupting), and high-speed
high-current interrupting control outputs that you can use to control circuit break-
ers and other devices in an equipment bay or substation control house.
=>
FILE DIR REPORTS <Enter>
BRE_1.TXT R
BRE_2.TXT R
BRE_S1.TXT R
BRE_S2.TXT R
CBRE.TXT R
CHISTORY.TXT R
CPRO.TXT R
CSER.TXT R
HISTORY.TXT R
PRO.TXT R
SER.TXT R
=>
Figure 3.54
Example Reports File Structure
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...