5.9
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Functions
Current and Voltage Source Selection
ESS := 2, Single Circuit Breaker Configuration—Two Current Inputs
Set ESS to 2 for single circuit breaker applications using two current sources.
illustrates this application along with the corresponding current and
voltage sources. The relay uses current source IW for line relaying and current
source IX for Circuit Breaker 1 failure protection.
ESS := 3, Double Circuit Breaker Configuration—Independent Current Inputs
Set ESS to 3 for circuit breaker-and-a-half applications using independent current
sources.
illustrates this application along with the corresponding cur-
rent and voltage sources. This selection provides independent circuit breaker fail-
ure protection for Circuit Breaker 1 and Circuit Breaker 2.
ALINEV
Alternate Line Voltage Source (VZ, NA)
NA
ALTV
Alternate Voltage Source (SEL
OGIC
Equation)
NA
Hidden
a
Hidden when preceding setting is NA.
Table 5.6
ESS := 1, Current and Voltage Source Selection (Sheet 2 of 2)
Setting
Prompt
Entry
Comments
Figure 5.6
ESS := 2, Single Circuit Breaker Configuration
Table 5.7
ESS := 2, Current and Voltage Source Selection
Setting
Prompt
Entry
Comments
NUMBK
Number of Circuit Breakers in Scheme (1, 2)
1
LINEI
Line Current Source (IW)
IW
Automatic
ALINEI
Alternate Line Current Source (IX, NA)
NA
ALTI
Alternate Current Source (SEL
OGIC
Equation)
NA
Hidden
a
a
Hidden when preceding setting is NA.
BK1I
Breaker 1 Current Source (IX)
IX
Automatic
BK2I
Breaker 2 Current Source (NA)
NA
Hidden
IPOL
Polarizing Current (NA)
NA
Automatic
ALINEV
Alternate Line Voltage Source (VZ, NA)
NA
ALTV
Alternate Voltage Source (SEL
OGIC
Equation)
NA
Hidden
SEL-421 Relay
BUS
CB1
3
1
3
IW
IX
VAZ
VY
3
Analog Input
IW
IX
VY
VAZ
Function
CB1 protection, line protection
CB1 breaker failure
Line protection
Synchronism check
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...