SEL-400 Series Relays
Control
Disconnect Logic
89CIR
m
, 89OIR
m
The 89CIR
m
and 89OIR
m
SEL
OGIC
control equations provide the flexibility to
customize resetting the Close and Open Immobility Timers. By default, 89CIR
m
is set to NOT 89OPN
m
, and 89OIR
m
is set to NOT 89CL
m
.
89CL
m
, 89OPN
m
The 89CL
m
and 89OPN
m
Relay Word bits report the state of the disconnect
switches. If the disconnect switch is closed, Relay Word bit 89CL
m
is asserted; if
the disconnect switch is open, Relay Word bit 89OPN
m
is asserted. See
for a description of these inputs.
Disconnect Switch Close and Open Control Logic Action Inputs
89CCN
m
, 89OCN
m
89CCN
m
and 89OCN
m
SEL
OGIC
control equations are for programmable close
and open disconnect switch operations. The LOCAL Relay Word bit must be
deasserted for the SEL
OGIC
close or open to initiate a disconnect switch opera-
tion. Use care when using SEL
OGIC
control equations for disconnect switch oper-
ations; this disconnect operate method is not supervised by the breaker jumper or
appropriate relay access levels as is the case with other disconnect operation
methods.
89CCM
m
, 89OCM
m
89CCM
m
and 89OCM
m
Relay Word bits pulse for one-quarter cycle when close
or open disconnect operations are executed from the one-line diagram on the
front-panel screen. The LOCAL Relay Word bit must be asserted, for Relay
Word bits 89CCM
m
or 89OCM
m
to assert.
89CC
m
, 89OC
m
The
89CLOSE
command or Fast Operate disconnect close message, pulses
Relay Word bit 89CC
m
for one-quarter cycle. The
89OPEN
command or Fast
Operate disconnect open message, pulses Relay Word bit 89OC
m
for one-quarter
cycle. The LOCAL Relay Word bit must be deasserted for a disconnect switch
operation to be initiated by a Fast Operate message or
89CLOSE
and
89OPEN
commands.
Disconnect Switch Close and Open Immobility Timer Logic Settings
89CIT
m
, 89OIT
m
89CIT
m
and 89OIT
m
timer settings in the Bay settings class define the close and
open immobility timers.
Disconnect Switch Close and Open Immobility Timer Logic Outputs
89CIM
m
, 89OIM
m
When 89CIM
m
or 89OIM
m
asserts, the close or open immobility timer has
expired.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...